  1. A transformer nameplate shows a BIL of 150 kV. During an applied voltage test, the correct test voltage per NETA MTS would be applied for:

    Answer: 1 minute

    NETA MTS specifies that applied (hi-pot) voltage tests on transformers are held for 1 minute at the rated test voltage.

  2. When interpreting DGA results using the Rogers Ratio method, a ratio of CH4/H2 < 0.1 combined with C2H2/C2H4 < 0.1 is most consistent with:

    Answer: Partial discharge (corona)

    The Rogers Ratio pattern with low CH4/H2 and very low C2H2/C2H4 is characteristic of partial discharge or corona activity.

  3. During a transformer load tap changer (LTC) resistance test, erratic resistance readings across tap positions most likely indicate:

    Answer: Worn or pitted contacts within the LTC

    Erratic or inconsistent resistance across LTC tap positions is a classic sign of worn, pitted, or dirty tap changer contacts.

  4. The Karl Fischer titration method is used in transformer testing to determine:

    Answer: Water content in transformer oil (ppm)

    The Karl Fischer titration is the standard chemical method for precisely measuring water (moisture) content in transformer insulating oil in parts per million.

  5. A three-winding transformer is tested for short-circuit impedance. Which winding combination provides the impedance between the primary and tertiary windings?

    Answer: Short the tertiary, energize the primary, measure impedance

    To measure primary-to-tertiary impedance, the tertiary is short-circuited, voltage is applied to the primary, and impedance is calculated from the measured values.

  6. What does a low interfacial tension (IFT) value in transformer oil testing indicate?

    Answer: Oil contains polar contaminants or oxidation by-products

    Low IFT values in transformer oil indicate the presence of polar contaminants such as oxidation products, sludge precursors, or soluble decay products from insulating materials.

  7. During a transformer core ground test, the insulation resistance between the core and ground reads zero. This finding indicates:

    Answer: Multiple core grounds exist, creating a circulating current loop

    A transformer core should have only one intentional ground point; a zero reading when testing the isolated core connection indicates an unintended additional ground, forming a loop that allows circulating currents.