Protective Relay Applications Flashcards
7 cards from real NETA practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 Protective Relay Applications flashcards as text
What is the primary function of a distance relay (21) in transmission line protection?
Answer: Measure impedance to the fault location
A distance relay measures the impedance from the relay location to the fault, using both voltage and current inputs to determine fault location.
Which relay characteristic is best suited for protecting a transformer against internal turn-to-turn faults?
Answer: Differential relay (87)
The differential relay (87) compares current entering and leaving the transformer; internal faults cause an imbalance that triggers tripping.
In a Mho distance relay, the operating characteristic on an R-X diagram is shaped like a:
Answer: Circle passing through the origin
The Mho relay characteristic is a circle on the R-X diagram that passes through the origin, providing inherent directionality.
What does the term 'reach' mean in the context of a distance relay?
Answer: The impedance setting that defines the protected zone boundary
Reach is the impedance value (in ohms) up to which the relay will operate, defining the boundary of the protection zone.
A pilot protection scheme uses communications between line terminals primarily to:
Answer: Achieve high-speed tripping for faults anywhere on the protected line
Pilot schemes use communications to allow both terminals to trip simultaneously for internal faults, achieving high-speed protection for the full line length.
Which type of bus protection scheme uses current from all feeders connected to the bus and compares them?
Answer: Differential bus protection (87B)
Differential bus protection sums all currents flowing into and out of the bus; any difference indicates an internal fault.
What is the purpose of a check zone in high-impedance bus differential protection?
Answer: To provide a redundant differential element covering all bus sections
The check zone covers all bus sections and must operate simultaneously with a zone element, preventing false trips due to CT errors.