โ† All NETA Flashcard Decks

Protective Relay Applications Flashcards

7 cards from real NETA practice questions. Tap to flip, then mark Knew It or Still Learning โ€” missed cards come back until you master them.

Read the first 7 Protective Relay Applications flashcards as text
  1. What is the primary function of a distance relay (21) in transmission line protection?

    Answer: Measure impedance to the fault location

    A distance relay measures the impedance from the relay location to the fault, using both voltage and current inputs to determine fault location.

  2. Which relay characteristic is best suited for protecting a transformer against internal turn-to-turn faults?

    Answer: Differential relay (87)

    The differential relay (87) compares current entering and leaving the transformer; internal faults cause an imbalance that triggers tripping.

  3. In a Mho distance relay, the operating characteristic on an R-X diagram is shaped like a:

    Answer: Circle passing through the origin

    The Mho relay characteristic is a circle on the R-X diagram that passes through the origin, providing inherent directionality.

  4. What does the term 'reach' mean in the context of a distance relay?

    Answer: The impedance setting that defines the protected zone boundary

    Reach is the impedance value (in ohms) up to which the relay will operate, defining the boundary of the protection zone.

  5. A pilot protection scheme uses communications between line terminals primarily to:

    Answer: Achieve high-speed tripping for faults anywhere on the protected line

    Pilot schemes use communications to allow both terminals to trip simultaneously for internal faults, achieving high-speed protection for the full line length.

  6. Which type of bus protection scheme uses current from all feeders connected to the bus and compares them?

    Answer: Differential bus protection (87B)

    Differential bus protection sums all currents flowing into and out of the bus; any difference indicates an internal fault.

  7. What is the purpose of a check zone in high-impedance bus differential protection?

    Answer: To provide a redundant differential element covering all bus sections

    The check zone covers all bus sections and must operate simultaneously with a zone element, preventing false trips due to CT errors.