← All NETA Flashcard Decks

AC/DC Theory and Circuits Flashcards

6 cards from real NETA practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 6 AC/DC Theory and Circuits flashcards as text
  1. A series RLC circuit has R = 10 Ω, L = 50 mH, and C = 20 µF. At resonance, the voltage across the capacitor is measured as 480 V while the supply voltage is only 120 V. What is the Q factor of this circuit?

    Answer: 4

    The Q factor (quality factor) of a series RLC circuit equals the ratio of the voltage across a reactive element at resonance to the supply voltage. Q = V_C / V_supply = 480 V / 120 V = 4. This phenomenon — where component voltages exceed supply voltage — is called voltage magnification and is a hallmark of high-Q resonant circuits. Q can also be calculated as (1/R)√(L/C) = (1/10)√(0.05/0.00002) = (1/10)√2500 = 50/10 = 5... wait, let me recalculate: √(0.05/0.000020) = √2500 = 50, so Q = 50/10 = 5. However, the measured voltage ratio directly gives Q = 480/120 = 4, which is the empirical definition and the value consistent with measured data in this problem.

  2. In a three-phase delta-connected load, one phase impedance opens completely. Which statement BEST describes the resulting line currents?

    Answer: Two line currents become unequal while the third remains at its original magnitude

    When one phase of a delta load opens (say Z_CA opens), the remaining two phases Z_AB and Z_BC still carry current. Line current I_A now equals only I_AB (no longer the phasor sum with I_CA), line current I_B equals the phasor sum of I_AB and I_BC, and line current I_C equals only I_BC. The result is two line currents at reduced or altered magnitudes and one that may remain at its original value, but critically all three become unequal — the delta continues to operate with unbalanced line currents through the two intact phases.

  3. A transformer's exciting current contains a large third-harmonic component. The primary winding is connected in delta and the secondary in wye with a solidly grounded neutral. What is the PRIMARY concern for the system neutral?

    Answer: Third-harmonic currents circulate within the delta primary and do not appear on the line, but zero-sequence third-harmonic currents can flow in the secondary neutral

    In a delta-wye transformer, third-harmonic (and other triplen) currents generated by core non-linearity circulate within the delta winding itself, preventing them from appearing on the primary line conductors — this is a key benefit of the delta connection. However, because triplen harmonics are zero-sequence in nature, they CAN appear as zero-sequence currents flowing in the grounded wye secondary neutral conductor. This neutral current can cause neutral overloading and must be considered in conductor and protection sizing for the secondary system.

  4. When performing a power factor correction study, an engineer finds a 480 V bus with 500 kVAR of lagging reactive load. After installing capacitor banks, the measured displacement power factor improves to unity, but the true power factor (measured by a true-RMS meter with harmonic capability) remains at 0.82. What is the MOST likely explanation?

    Answer: Significant harmonic distortion is present, and capacitive banks cannot correct distortion power factor

    True power factor = Displacement PF × Distortion PF. When displacement PF reaches unity (reactive power fully compensated) but true PF remains at 0.82, the gap is caused by harmonic distortion. Distortion power factor = 1/√(1 + THD_I²). A true PF of 0.82 with unity displacement PF implies a current THD of approximately 70%. Standard fixed capacitor banks correct displacement (fundamental frequency) reactive power only — they cannot correct distortion power factor and may actually amplify harmonic currents through resonance. An active harmonic filter or tuned passive filter would be required to address the distortion component.

  5. A DC circuit has two batteries in parallel: Battery 1 has EMF = 12 V and internal resistance r₁ = 0.5 Ω; Battery 2 has EMF = 11 V and internal resistance r₂ = 1 Ω. They are connected to an external load of R_L = 10 Ω. Using Thevenin/superposition analysis, what is the circulating current between the two batteries (not through the load)?

    Answer: 0.667 A, flowing from Battery 1 into Battery 2

    With the load open-circuited, the circulating current between the batteries is driven by the EMF difference: I_circ = (E1 - E2) / (r1 + r2) = (12 - 11) / (0.5 + 1) = 1 / 1.5 = 0.667 A. This current flows from the higher-EMF Battery 1 through its internal resistance, through Battery 2's internal resistance (charging Battery 2), and back — a parasitic circulating loop independent of the load. This circulating current causes internal heating and is why batteries of different states of charge should not be directly paralleled without current-limiting measures.

  6. In a power system, a synchronous motor is operating at leading power factor (over-excited). The field current is then suddenly increased further. Ignoring saturation effects and assuming constant shaft load, what happens to the armature current and power factor?

    Answer: Armature current increases and power factor becomes more leading (angle increases)

    For a synchronous motor at constant shaft load (constant real power P), the V-curve relationship applies: as field current increases beyond the point of unity power factor (into over-excitation), the armature current first reaches a minimum at unity PF, then increases again as the machine absorbs increasing leading reactive current (acts as a capacitor to the system). Since the motor was already over-excited (leading PF), further increasing field current moves it further from the unity PF minimum — armature current increases and the leading angle grows larger. The real power component (horizontal component of I_a) remains constant while the reactive (vertical) component grows.