  1. What is the maximum total degrees of bends permitted in a run of EMT between pull points?

    Answer: 360 degrees

    NEC 358.26 limits bends between pull points to the equivalent of four quarter bends, or 360 degrees total.

  2. EMT must be securely fastened within what distance of each outlet box, junction box, or conduit termination?

    Answer: 3 feet

    NEC 358.30(A) requires EMT to be fastened within 3 ft of each box or termination and at least every 10 ft.

  3. Type NM cable run along framing members must be secured within what distance of every cable entry into an enclosure that has cable clamps?

    Answer: 12 inches

    NEC 334.30 requires NM cable to be secured within 12 in of each box or fitting and at intervals not exceeding 4.5 ft.

  4. When NM cable enters a single-gang nonmetallic box that has no cable clamps, within what distance of the box must the cable be secured?

    Answer: 8 inches

    Article 314 allows a single-gang nonmetallic box without clamps only when the cable is secured within 8 in of the box.

  5. Per Table 300.5, what is the minimum cover for Type UF cable buried directly in the earth with no other protection, under general conditions?

    Answer: 24 inches

    Column 1 of Table 300.5 requires 24 in of cover for direct-buried cables or conductors.

  6. What is the minimum bending radius for Type NM cable?

    Answer: 5 times the cable diameter

    NEC 334.24 requires that bends in NM cable have a radius of at least five times the cable's diameter.

  7. At each outlet box, at least how much free conductor must extend from the point where the conductor emerges from its raceway or cable sheath?

    Answer: 6 inches

    NEC 300.14 requires at least 6 in of free conductor, plus 3 in outside the box when the opening is less than 8 in.