What is the maximum overcurrent device rating permitted for a branch circuit supplying a 15-ampere receptacle on a single circuit?
Answer: 15 A
A single 15-ampere receptacle on an individual branch circuit must not exceed a 15-ampere overcurrent device.
On a 20-ampere multi-outlet branch circuit, what ampere ratings of receptacles are permitted per NEC Table 210.21(B)(3)?
Answer: 15 or 20 A
A 20-ampere circuit may serve receptacles rated 15 or 20 amperes.
What is the minimum branch-circuit rating for a fixed appliance that is not a motor-operated load rated over 50% of the circuit?
Answer: Equal to or greater than the appliance load
The branch-circuit rating must not be less than the load it supplies.
When a branch circuit supplies a continuous load, the overcurrent device must be rated at least what percent of the continuous load?
Answer: 125%
NEC 210.20(A) requires the OCPD to be sized at 125% of the continuous load.
A bathroom in a dwelling requires a branch circuit of what minimum rating dedicated to its receptacles?
Answer: 20 A
NEC 210.11(C)(3) requires at least one 20-ampere circuit for bathroom receptacle outlets.
What is the calculated load in amperes for a 1500 VA laundry circuit at 120 V?
Answer: 12.5 A
1500 VA / 120 V = 12.5 A.
A 240-volt, 30-ampere branch circuit serving a single fixed appliance can deliver a maximum continuous load of how many amperes?
Answer: 24 A
Continuous loads are limited to 80% of the rating: 30 A x 0.80 = 24 A.