Load Calculations & Branch Circuits Flashcards
7 cards from real NEC practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 Load Calculations & Branch Circuits flashcards as text
What is the minimum general lighting load per square foot for a dwelling unit per NEC Table 220.12?
Answer: 3 VA
Dwelling units use a general lighting load of 3 VA per square foot under the standard calculation method.
How many small-appliance branch circuits are required as a minimum in a dwelling kitchen?
Answer: 2
NEC 210.11(C)(1) requires at least two 20-ampere small-appliance branch circuits for the kitchen, pantry, and dining areas.
A 20-ampere branch circuit at 120 volts has a maximum continuous load rating of how many amperes?
Answer: 16 A
Continuous loads are limited to 80% of the circuit rating, so 20 A x 0.80 = 16 A.
What VA value is used for each small-appliance and laundry branch circuit in the standard dwelling calculation?
Answer: 1500 VA
NEC 220.52 requires a minimum of 1500 VA for each small-appliance and laundry branch circuit.
Under the standard method, what demand factor applies to the dwelling general lighting load above the first 3000 VA up to 120,000 VA?
Answer: 35%
Per NEC Table 220.42, the portion from 3001 to 120,000 VA is taken at 35%.
What is the minimum size THHN copper conductor permitted for a 20-ampere branch circuit?
Answer: 12 AWG
A 20-ampere branch circuit requires a minimum 12 AWG copper conductor.
Receptacles in a dwelling are generally NOT counted as load in the standard calc because they are covered by which allowance?
Answer: General lighting load
In dwellings the general lighting load (3 VA/sq ft) covers general-use receptacle outlets, so they aren't added separately.