Branch Circuit Requirements Flashcards
7 cards from real NEC practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 Branch Circuit Requirements flashcards as text
A multiwire branch circuit must have a means to simultaneously disconnect which conductors at the point of origin?
Answer: All ungrounded conductors
NEC 210.4(B) requires simultaneous disconnection of all ungrounded conductors of a multiwire branch circuit.
In a multiwire branch circuit, the grounded (neutral) conductor carries what current when loads are balanced?
Answer: The difference of the phase currents
On a balanced multiwire circuit the neutral carries only the unbalanced (difference) current.
Where must the ungrounded and grounded conductors of each multiwire branch circuit be grouped?
Answer: At the point of origin
NEC 210.4(D) requires conductors of each multiwire branch circuit to be grouped at the point of origin.
The continuity of a grounded conductor in a multiwire branch circuit must not depend on which connection?
Answer: A device terminal such as a receptacle
NEC 300.13(B) prohibits relying on device terminals for neutral continuity in multiwire circuits.
Each branch circuit shall be legibly identified at the panelboard as to its what?
Answer: Purpose or use
NEC 408.4(A) requires each circuit to be marked with its clear, evident purpose.
Branch-circuit ungrounded conductors must be identifiable by which means where a premises has more than one nominal voltage system?
Answer: Phase and system identification by color or marking
NEC 210.5(C) requires ungrounded conductors to be identified by phase/system where multiple voltage systems exist.
What is the maximum number of multiwire branch-circuit ungrounded conductors that share a common neutral in a typical 120/240-volt single-phase system?
Answer: Two
A 120/240V single-phase multiwire circuit uses two ungrounded conductors sharing one neutral.