Branch Circuit Requirements Flashcards
7 cards from real NEC practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Branch Circuit Requirements flashcards as text
How many small-appliance branch circuits are required for receptacle outlets in a dwelling kitchen, pantry, and dining area?
Answer: At least two
NEC 210.11(C)(1) requires at least two 20-amp small-appliance branch circuits.
At least one 20-ampere branch circuit must be provided for receptacles in which dwelling location?
Answer: Laundry area
NEC 210.11(C)(2) requires a dedicated 20-amp laundry branch circuit.
The small-appliance branch circuits in a dwelling kitchen are NOT permitted to supply which of the following?
Answer: Lighting outlets
NEC 210.52(B)(2) prohibits small-appliance circuits from supplying lighting outlets.
A dwelling-unit bathroom requires at least one branch circuit of what rating for its receptacle outlets?
Answer: 20 amperes
NEC 210.11(C)(3) requires a 20-amp branch circuit for bathroom receptacles.
When a single 20-amp branch circuit supplies the bathroom receptacles in a dwelling, what else may it supply?
Answer: Only receptacles in that one bathroom
Per NEC 210.11(C)(3) Exception, a circuit serving one bathroom may also feed that bathroom's other equipment, but a multi-bathroom circuit must serve receptacles only.
What is the minimum number of general-purpose branch circuits determined by, in a dwelling unit?
Answer: Square footage at 3 VA per ft² for lighting
NEC 220.12 uses 3 VA per square foot to compute the general lighting load that sets circuit count.
A 125-volt, 20-amp branch circuit serving the laundry is permitted to supply which additional location?
Answer: Only laundry receptacles
NEC 210.11(C)(2) restricts the laundry branch circuit to laundry receptacle outlets only.