NEC Cheat Sheet 2026

The 30 highest-yield NEC facts, distilled from real exam questions. Print it, save it as a PDF, or study it here — free, no sign-up.

80 questions
240 min time limit
70% to pass
  1. The continuity of a grounded conductor in a multiwire branch circuit must not depend on which connection? A device terminal such as a receptacle
  2. What size service conductors are needed for a 190 A calculated load in a dwelling? The service disconnect breaker has a 200-amp rating. 2/0 AWG
  3. What is a common cause of electrical fires? Overloaded circuits.
  4. According to the NEC, Class II hazardous locations are characterized by the presence of which hazardous substance? Combustible dust
  5. Why is it important to properly size the overcurrent protection for a branch circuit? To prevent overloading and ensure safety in case of faults.
  6. Motor feeder tap conductors that are not more than ___ length must have an ampacity that is at least ten times the feeder protection device's rating. 10 ft
  7. How do you calculate the total amperage for a branch circuit? Dividing the total wattage by the circuit voltage.
  8. In Table 310.16, what is the ampacity of 1/0 AWG copper THHN at 90°C? 170 amps
  9. What is the minimum height clearance for overhead service-drop conductors above a residential driveway? 12 feet
  10. Per NEC 210.52, receptacle outlets in a dwelling kitchen counter are required so no point along the wall line is more than what distance from a receptacle? 24 inches
  11. Which NEC chapter contains the tables for conductor properties, conduit fill, and similar reference data? Chapter 9
  12. What is the standard burial depth for a residential 120/240V branch circuit in rigid metal conduit (RMC)? 6 in
  13. The neutral conductor in a properly wired system should be bonded to ground at: Only the service equipment/main panel
  14. When a single 20-amp branch circuit supplies the bathroom receptacles in a dwelling, what else may it supply? Only receptacles in that one bathroom
  15. Using the optional method, which load is taken at the larger of 100% of A/C or 65% of central electric heating? Heating/cooling
  16. Unless specifically permitted otherwise, what is the maximum overcurrent protection allowed for a 12 AWG copper conductor according to NEC 240.4(D)? 20A
  17. Which of the following should not be placed over a stairway step? overcurrent devices
  18. Which NEC requirement ensures a service disconnect can be operated without reaching over energized parts? Readily accessible location
  19. What is the maximum support spacing for 1/2-inch rigid metal conduit (RMC) running horizontally and secured? 10 feet
  20. The metal underground water pipe electrode must be in direct contact with earth for at least how many feet? 10 ft
  21. What is the main purpose of the NEC's grounding requirements? To increase the efficiency of the electrical system.
  22. GFCI protection is required for 125-volt, 15- and 20-ampere receptacles installed in which dwelling location? Garages
  23. What is the demand factor allowed for the first 3,000 VA of general lighting load in a dwelling? 100%
  24. Which NEC article covers hazardous (classified) locations? Article 500
  25. What is the standard voltage used in most residential electrical systems in the U.S.? 120 volts.
  26. The required working clearance in front of electrical equipment operating at 120/240 volts is generally a minimum of: 36 inches
  27. In Class I, Division 1 hazardous locations, threaded conduit connections must have at minimum how many threads fully engaged per NEC 501.10(A)(1)? 5 threads
  28. Which of the following is a correct definition from the NEC? Grounded conductor
  29. A concrete-encased electrode (Ufer ground) must use at least how much bare rebar or copper conductor? 20 ft
  30. The grounded conductor brought to a separately derived system must be bonded: At the source or first disconnect
Turn these facts into recall: