  1. A 3-phase, 4-wire, 208Y/120V service supplies a balanced 3-phase load of 90 kVA. What is the line current?

    Answer: 180 A

    I = VA ÷ (V × √3) = 90,000 ÷ (208 × 1.732) = 249.9 ÷ 1.38 ≈ 249.9; corrected: 90,000 ÷ 360.3 = 249.9 ≈ 250 A — answer B.

  2. Per NEC 230.79, a single-family dwelling service must have a minimum rating of what amperage?

    Answer: 100 A

    NEC 230.79(C) requires a minimum 100-ampere service for single-family dwellings.

  3. When using the optional calculation for an existing dwelling per NEC 220.82, which loads are NOT included in the total connected load?

    Answer: Small appliance circuits

    Under NEC 220.82, small appliance branch circuits are included as a set load, but the calculation uses nameplate ratings and specific listed loads — all mandatory loads are included.

  4. A feeder neutral is allowed a 70% demand factor on that portion of the unbalanced load exceeding 200A per NEC 220.61(B). This reduction applies to what types of loads?

    Answer: Balanced three-phase loads

    NEC 220.61(B) allows the 70% neutral reduction on the portion exceeding 200A for other than non-linear loads and discharge lighting.

  5. A 480V, 3-phase motor has a full-load current of 27A. What is the minimum feeder ampacity required for this motor alone?

    Answer: 33.75 A

    Per NEC 430.24, the feeder must be at least 125% of the largest motor FLC: 27A × 1.25 = 33.75A.

  6. When calculating the service load for a dwelling with a 10 kW heat pump and a 6 kW electric furnace, which load is used in the service calculation?

    Answer: The larger of the two loads

    NEC 220.82(C)(5) requires that the larger of the heating or cooling load be used, not both simultaneously.

  7. A 120/240V single-phase service feeder supplies two 240V loads of 8,000W each and a 120V load of 3,000W. What is the neutral current?

    Answer: 12.5 A

    The 240V loads place no current on the neutral; the 120V load = 3,000W ÷ 120V = 25A on one leg, so neutral carries 12.5A unbalanced current.