  1. What is the maximum standard fuse or circuit breaker size permitted for a 10 AWG copper conductor with 30A ampacity used in a branch circuit?

    Answer: 30 amperes

    Per NEC 240.4(D), 10 AWG copper conductors are protected at a maximum of 30 amperes.

  2. A 240-volt, single-phase motor draws 28 amperes at full load. What is the maximum rating of an inverse-time circuit breaker permitted for branch-circuit protection of this motor?

    Answer: 70 amperes

    NEC 430.52 allows inverse-time breakers up to 250% of FLC for single-phase motors, and 28A × 2.5 = 70A.

  3. Which NEC article governs overcurrent protection for panelboards?

    Answer: Article 408

    NEC Article 408 covers switchboards, switchgear, and panelboards, including their overcurrent protection requirements.

  4. A 20-ampere, 120-volt branch circuit supplies a single receptacle. What is the minimum ampere rating required for that receptacle?

    Answer: 20 amperes

    NEC 210.21(B)(1) requires a single receptacle on a branch circuit to have an ampere rating not less than the branch-circuit rating.

  5. When is it permissible to use the next higher standard OCPD size above a conductor's ampacity?

    Answer: When the conductor ampacity does not correspond to a standard OCPD rating

    NEC 240.4(B) allows the next higher standard OCPD rating when the conductor's ampacity does not correspond to a standard rating, provided the OCPD is 800A or less.

  6. A service entrance has a calculated load of 175 amperes. Which standard-size OCPD is the smallest that may be used to protect this service?

    Answer: 200 amperes

    Standard OCPD sizes per NEC 240.6 jump from 175A to 200A, so 200A is the next available standard size above 175A.

  7. Type S fuses are designed to prevent which of the following problems?

    Answer: Overfusing by substituting a higher-rated fuse

    Type S fuses have a rejection feature that prevents inserting a fuse rated higher than the adapter allows, stopping overfusing.