Journeyman Electrician's Grounding and Bonding Flashcards

7 cards from real Journeyman Electrician’s Exam practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 7 Journeyman Electrician's Grounding and Bonding flashcards as text
  1. What is the minimum size equipment grounding conductor required for a 60-ampere circuit protected by a 60A breaker per NEC Table 250.122?

    Answer: 10 AWG copper

    Per NEC Table 250.122, a 60A overcurrent device requires a minimum 10 AWG copper equipment grounding conductor.

  2. Which NEC article primarily covers grounding and bonding requirements?

    Answer: Article 250

    NEC Article 250 covers all grounding and bonding requirements for electrical systems.

  3. A grounding electrode conductor is used to connect the grounded conductor to the:

    Answer: Grounding electrode system

    The grounding electrode conductor connects the grounded (neutral) conductor or equipment to the grounding electrode system.

  4. What is the purpose of bonding in an electrical system?

    Answer: To establish electrical continuity between conductive parts

    Bonding establishes electrical continuity and conductivity between conductive parts to ensure a low-impedance path for fault current.

  5. When installing a grounding electrode conductor in a metal raceway, what additional bonding requirement applies?

    Answer: Both ends of the raceway must be bonded to the conductor

    Per NEC 250.64(E), metal raceways enclosing a grounding electrode conductor must be bonded at both ends to the conductor.

  6. Which of the following may NOT be used as a grounding electrode per NEC 250.52?

    Answer: Metal underground gas piping system

    Per NEC 250.52(B)(1), underground gas piping systems are specifically prohibited as grounding electrodes.

  7. What is the maximum resistance allowed for a single-rod grounding electrode before a supplemental electrode is required per NEC 250.56?

    Answer: 25 ohms

    Per NEC 250.56, if a single rod, pipe, or plate electrode has a resistance exceeding 25 ohms, a supplemental electrode must be added.