  1. What is the standard take-up (deduct) for making a 90-degree bend in 1/2" EMT conduit?

    Answer: 5 inches

    The standard take-up for 1/2" EMT is 5 inches; subtract this from the desired stub height to locate the bend mark on the conduit.

  2. To bend a 45-degree offset with a rise of 6 inches, what is the distance between the two bend marks?

    Answer: 8.48 inches

    Distance = 6 x 1.414 (the multiplier for 45-degree bends) = 8.48 inches between the two marks.

  3. Which multiplier is applied to the offset height when bending a 30-degree offset?

    Answer: 2.000

    A 30-degree offset uses a multiplier of 2.000 because 1 divided by sin(30 degrees) = 1 divided by 0.5 = 2.000.

  4. What is the standard take-up for a 90-degree bend in 3/4" EMT?

    Answer: 6 inches

    The standard take-up for 3/4" EMT is 6 inches for a 90-degree stub-up bend.

  5. You need a 90-degree stub-up of 14 inches in 1" EMT (take-up = 8 inches). Where should the bend mark be placed from the end of the conduit?

    Answer: 6 inches

    Mark location = desired stub height minus take-up = 14 minus 8 = 6 inches from the end of the conduit.

  6. Per the NEC, what is the maximum total degrees of bends permitted in conduit between pull points?

    Answer: 360 degrees

    NEC Sections 358.26, 344.26, and similar articles limit total bends to 360 degrees (equivalent of four 90-degree bends) between pull points.

  7. Which NEC article governs the installation of Rigid Metal Conduit (RMC)?

    Answer: Article 344

    NEC Article 344 covers Rigid Metal Conduit (RMC) installation requirements.