Journeyman Electrician's Conductor Sizing and Ampacity Flashcards

7 cards from real Journeyman Electrician’s Exam practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 7 Journeyman Electrician's Conductor Sizing and Ampacity flashcards as text
  1. A 120/240V single-phase service uses 2 AWG copper conductors. What is the standard ampacity of 2 AWG copper at 75°C per NEC Table 310.15(B)(16)?

    Answer: 115A

    2 AWG copper conductors have a standard ampacity of 115A at 75°C per NEC Table 310.15(B)(16).

  2. Three current-carrying conductors are bundled in a conduit. According to NEC 310.15(C)(1), what adjustment factor applies?

    Answer: No adjustment needed

    NEC 310.15(C)(1) requires no adjustment factor for 3 or fewer current-carrying conductors.

  3. Which conductor material has higher conductivity, requiring a smaller gauge for equivalent ampacity?

    Answer: Copper

    Copper has higher conductivity than aluminum, so it carries more current at the same wire gauge.

  4. A feeder supplies a continuous load of 80A. What is the minimum conductor ampacity required before applying breaker sizing?

    Answer: 100A

    Conductors for continuous loads must be sized at 125% of the load (80A × 1.25 = 100A) per NEC 215.2.

  5. What NEC table is used to find the ampacity of conductors 0-2000V with not more than 3 current-carrying conductors in a raceway?

    Answer: Table 310.15(B)(16)

    NEC Table 310.15(B)(16) provides ampacity values for conductors up to 2000V with no more than 3 current-carrying conductors.

  6. A 6 AWG aluminum conductor has what standard ampacity at 75°C per NEC Table 310.15(B)(16)?

    Answer: 65A

    6 AWG aluminum at 75°C has an ampacity of 65A per NEC Table 310.15(B)(16).

  7. When using THWN-2 insulation at 75°C in a wet location, which temperature column applies for ampacity from NEC Table 310.15(B)(16)?

    Answer: 75°C column

    When equipment terminations are rated 75°C, the 75°C column must be used even if the insulation is rated higher.