  1. What is the maximum allowable cord-and-plug connected load on a 15-ampere receptacle outlet?

    Answer: 12 amperes

    NEC 210.21(B)(2) limits the load on a 15-ampere receptacle to 12 amperes (80% of rating) for cord-and-plug connected loads.

  2. A branch circuit supplying a 10 kW, 240-volt electric range in a dwelling unit must have conductors rated at least:

    Answer: 40 amperes

    Per NEC Table 220.55 and 210.19, a 10 kW range requires a minimum 40-ampere circuit with 8 AWG copper conductors.

  3. Which type of branch circuit is permitted to supply fixed electric space heating equipment?

    Answer: Individual or general-purpose branch circuit, per NEC

    NEC 424.3 allows fixed electric space heating to be supplied by either an individual or general-purpose branch circuit.

  4. For a branch circuit supplying show window lighting in a commercial occupancy, the NEC requires a load calculation of at least:

    Answer: 180 VA per linear foot

    NEC 220.14(G) requires show window lighting to be calculated at 180 VA per linear foot of show window.

  5. A 15-ampere, 125-volt duplex receptacle on a 20-ampere circuit is permissible when:

    Answer: Two or more receptacles are on the circuit

    NEC 210.21(B)(3) permits 15-ampere receptacles on a 20-ampere circuit when two or more receptacles are installed.

  6. According to NEC 210.52, the maximum spacing between receptacle outlets along a wall in a dwelling unit living room is:

    Answer: 12 feet

    NEC 210.52(A)(1) requires receptacles to be placed so no point along any wall is more than 6 feet from a receptacle, meaning spacing cannot exceed 12 feet between receptacles.

  7. A bathroom branch circuit in a dwelling unit that serves only bathroom receptacles must be rated:

    Answer: 20 amperes

    NEC 210.11(C)(3) requires at least one 20-ampere branch circuit for bathroom receptacle outlets.