  1. What is the minimum size copper equipment grounding conductor required for a circuit protected by a 100-ampere overcurrent device?

    Answer: 8 AWG

    Per NEC Table 250.122, an 8 AWG copper EGC is required for circuits protected by overcurrent devices up to 100 amperes.

  2. A single 120-volt, 20-ampere kitchen small appliance circuit can serve a maximum of how many square feet of counter space?

    Answer: There is no square footage limit — two circuits are required regardless

    NEC 210.11(C)(1) requires at least two small-appliance branch circuits for kitchen countertop receptacles, regardless of counter area.

  3. What is the maximum voltage drop recommended by the NEC for a branch circuit?

    Answer: 3%

    NEC 210.19(A) informational note recommends that branch circuit voltage drop not exceed 3% for efficiency and performance.

  4. Which of the following is the correct formula to calculate the resistance of a conductor?

    Answer: R = V / I

    Ohm's Law states that resistance equals voltage divided by current (R = V/I), the fundamental relationship in electrical circuits.

  5. When sizing conductors for a continuous load, the conductor must be rated for at least what percentage of the continuous load?

    Answer: 125%

    NEC 210.19(A)(1) and 215.2(A)(1) require conductors supplying continuous loads to be sized at 125% of the continuous load current.

  6. What type of overcurrent protection is required for a motor with a full-load current of 28 amperes using an inverse time breaker?

    Answer: 35 amps

    NEC 430.52 and Table 430.52 allow an inverse time breaker at 250% of FLA for most AC motors; 28 × 2.5 = 70A, but the next standard size not exceeding is selected; however basic sizing is 125% for conductors, while breaker for motor is typically 250% FLA, next standard size = 70A.

  7. In a panelboard, what is the minimum clearance required between the top of the panel and the ceiling in a dedicated electrical space?

    Answer: The full height to the structural ceiling, minimum 6 feet

    NEC 110.26(E)(1) requires dedicated electrical equipment space extending from the floor to a height of 6 feet or the structural ceiling, whichever is lower.