  1. According to the NEC, what is the maximum number of current-carrying conductors allowed in a conduit before derating is required?

    Answer: 3

    The NEC allows up to 3 current-carrying conductors in a conduit without derating; more than 3 requires applying adjustment factors per Table 310.15(C)(1).

  2. A 20-ampere branch circuit receptacle outlet in a bathroom must be protected by which of the following?

    Answer: GFCI

    NEC 210.8 requires GFCI protection for all 125-volt, single-phase, 15- and 20-ampere receptacles in bathrooms.

  3. What is the minimum burial depth for a rigid metal conduit (RMC) under a residential driveway?

    Answer: 12 inches

    NEC Table 300.5 requires RMC to be buried at least 6 inches under a residential driveway, but under a concrete slab (like a driveway) it is 6 inches; under regular driveways it's 12 inches for RMC.

  4. Which conductor color is reserved exclusively for ungrounded (hot) conductors in a 3-phase, 4-wire delta system with a high leg?

    Answer: Orange

    NEC 230.56 and 408.3(F) require the high-leg conductor (which has a higher voltage to ground) to be identified with orange tape or insulation.

  5. What is the ampacity of a 10 AWG copper THHN conductor in free air at 60°C ambient?

    Answer: 55 amps

    Per NEC Table 310.15(B)(17), a 10 AWG THHN copper conductor in free air at 60°C has an ampacity of 55 amperes.

  6. When installing a service panel, what is the maximum number of disconnecting means allowed at one location?

    Answer: 6

    NEC 230.71(A) limits the number of service disconnecting means to a maximum of six switches or sets of fuses.

  7. In which location is flexible metal conduit (FMC) NOT permitted to be used?

    Answer: In wet locations without additional protection

    NEC 348.12(2) prohibits FMC in wet locations unless the conductors are approved for wet locations and the installation ensures liquid-tight conditions.