Journeyman Electrician’s Exam Cheat Sheet 2026
The 30 highest-yield Journeyman Electrician’s Exam facts, distilled from real exam questions. Print it, save it as a PDF, or study it here — free, no sign-up.
80 questions
240 min time limit
70% to pass
- What is the maximum number of disconnects permitted for a single service per NEC 230.71? → Six disconnects
- What is a "rolling offset" in conduit bending? → An offset that travels in two planes simultaneously, both vertically and horizontally
- A 120/240V single-phase service feeder supplies two 240V loads of 8,000W each and a 120V load of 3,000W. What is the neutral current? → 12.5 A
- What is the minimum clearance required in front of a panelboard with exposed live parts on one side only (Condition 1) per NEC 110.26(A)(1)? → 36 inches
- At a subpanel in a detached garage fed by a feeder from the house, which conductors must be run to the subpanel? → Hot, neutral, and a separate equipment grounding conductor
- GFCI protection is required for receptacles installed within how many feet of the inside walls of a permanently installed swimming pool at a dwelling unit? → 20 feet
- For industrial and commercial buildings, the required lighting load is ___ volt amperes per square foot: → 2
- What is the capacitive reactance (X_C) of a 100 μF capacitor at 60 Hz? → 26.5 Ω
- When a 480 Y/277 volt, three-phase, 4-wire electrical system is used to supply a commercial service with a 400 ampere rating, the service is rated as follows: → 332.5 kVA
- Per NEC 680.23(A)(1) and (A)(6), a replacement underwater pool luminaire must be: → Listed for use as a swimming pool luminaire and the installation must be watertight
- There will be a voltage drop of _______ V in a single phase, 240 V circuit with 3 AWG AI conductors powering a 40 A load 300' away from the power panel. → 9.67
- An outlet box installed in an outdoor location exposed to rain must be: → Listed for use in wet locations
- In a 3-phase, 4-wire wye system where the line-to-line voltage is 208V, what is the line-to-neutral (phase) voltage? → 120 volts
- In a commercial location, GFCI protection for 125-volt, 15- and 20-ampere receptacles is required in which area? → Kitchens, bathrooms, rooftops, and other specified locations
- Per NEC 240.6, which of the following is NOT a standard ampere rating for fuses and inverse time circuit breakers? → 35 amperes
- Equipment installed in Class I, Division 1 locations must be listed as: → Explosion-proof or intrinsically safe
- Per NEC Article 760, what equipment requirement applies to all fire alarm system wiring and devices? → Equipment and wiring must be listed for fire alarm service
- When is it permissible to use the next higher standard OCPD size above a conductor's ampacity? → When the conductor ampacity does not correspond to a standard OCPD rating
- Per NEC Chapter 9, Table 2, what is the minimum bending radius to the centerline for 2-inch EMT conduit with conductors that do not have a lead sheath? → 12 inches
- Flexible cord used with portable equipment in a hazardous Class I, Division 2 location must be: → Extra-hard-usage cord with grounding conductor
- NEC Article 500 classifies hazardous locations using which system? → Division system only
- Emergency system feeder conductors must have an ampacity sufficient to: → Handle all emergency loads that could be energized simultaneously
- What is the minimum overhead clearance required for service drop conductors above the water surface of a swimming pool? → 22.5 feet
- For a 240-volt, single-phase residential air conditioner with a nameplate rating of 24 amperes, what is the minimum branch circuit conductor ampacity? → 30 amps
- Per NEC 680.22(C), switching devices (light switches) near a pool must be located at least how far horizontally from the inside walls of the pool? → 5 feet
- What is the ampacity of 250 kcmil copper THHN at 90°C per NEC Table 310.15(B)(16)? → 290A
- Which of the following locations is explicitly prohibited for the installation of overcurrent devices, according to NEC 240.24? → In the bathrooms of dwelling units
- A circuit's ability to store electrical energy is known as . → Capacitance
- What is the maximum load permitted on a 20-ampere branch circuit serving general lighting and receptacles? → 16 amperes
- Where must the LINE terminals of a GFCI receptacle be connected? → To the source conductors coming from the panelboard
Turn these facts into recall:
What Practice Test Geeks adds beyond an AI chat for Journeyman Electrician’s Exam
An AI chatbot can quiz you, but it can't reproduce the exam conditions or keep your record. Here you get:
- A timed, full-length Journeyman Electrician’s Exam mock exam — 80 questions in 240 minutes with a 70% pass mark, modeled on the official exam's question count and time limit, followed by a score report broken down by exam domain.
- A fixed Journeyman Electrician’s Exam question bank: the same test every attempt, so your score is comparable from one try to the next instead of changing with every regenerated quiz.
- Progress saved on your device: completed tests, scores and missed questions stay in My Progress, so you can retake only what you got wrong.
- Journeyman Electrician’s Exam flashcards built from the same question bank.
- Free Journeyman Electrician’s Exam practice tests with the correct answer shown after each question.
Was this helpful?