  1. A single-family dwelling has a 200-amp, 240V service. What is the minimum service entrance conductor size required using 75°C copper conductors per NEC Table 310.12?

    Answer: 2/0 AWG copper

    NEC Table 310.12 allows 2/0 AWG copper at 75°C for a 200-amp service entrance.

  2. When calculating the demand load for electric ranges rated over 12 kW but not exceeding 27 kW in a dwelling, the NEC allows a maximum demand of 8 kW for one range, plus what percentage per additional kW over 12 kW?

    Answer: 5%

    Per NEC Table 220.55, for ranges over 12 kW, add 5% for each additional kW above 12 kW.

  3. A commercial building has 50 kVA of fluorescent lighting. Using standard demand factors, what minimum amperage feeder is required on a 208Y/120V, 3-phase system?

    Answer: 139 A

    50,000 VA ÷ (208V × 1.732) = 138.8 A, so a 139 A minimum feeder is required.

  4. Per NEC 220.82, the optional calculation for a single-family dwelling applies the first load increment of 10 kVA at 100%, then applies what demand factor to the remainder?

    Answer: 70%

    NEC 220.82(B) applies 100% to the first 10 kVA and 40% to the remainder of the total connected load.

  5. What is the minimum feeder size for a 60A, 240V single-phase load that operates continuously for more than 3 hours?

    Answer: 75 A

    Continuous loads must be sized at 125%, so 60A × 1.25 = 75A minimum feeder rating.

  6. In a multi-family dwelling with 20 units, each having a 12 kW electric range, what demand factor does NEC Table 220.55 Column C assign to 20 ranges?

    Answer: 38%

    NEC Table 220.55 Column C lists a 38% demand factor for 20 electric ranges.

  7. When sizing a service for a 2,400 sq ft single-family dwelling using the standard calculation method, what is the minimum general lighting load at 3 VA per square foot?

    Answer: 7,200 VA

    2,400 sq ft × 3 VA/sq ft = 7,200 VA for the general lighting load.