  1. Where must an overcurrent device be located relative to the point where a conductor receives its supply?

    Answer: At the point where the conductor receives its supply

    NEC 240.21 requires OCPDs to be placed at the point where the conductor receives its supply unless a tap rule exception applies.

  2. A feeder tap conductor using the 10-foot tap rule must have an ampacity of at least what percentage of the overcurrent device protecting the feeder?

    Answer: 33%

    NEC 240.21(B)(1) requires the tap conductor's ampacity to be at least one-third (33%) of the feeder OCPD rating for the 10-foot tap rule.

  3. Which of the following best describes an 'inverse-time' circuit breaker?

    Answer: It trips faster as the current increases

    An inverse-time breaker has a trip time that decreases as the overcurrent magnitude increases, providing time-current coordination.

  4. A fused disconnect for an air-conditioning unit must be installed within sight of and readily accessible from the unit. Which article covers this requirement?

    Answer: Article 440

    NEC Article 440 covers air-conditioning and refrigerating equipment, including the disconnecting means and overcurrent protection requirements.

  5. What is the maximum OCPD size allowed for a 15 AWG copper conductor used in a branch circuit?

    Answer: 15 amperes

    NEC 240.4(D)(3) limits the OCPD for 14 AWG to 15A; 15 AWG is not a standard branch-circuit size, so 14 AWG rules (15A max) apply.

  6. Ground-fault circuit interrupter (GFCI) protection detects current imbalances as small as:

    Answer: 5 milliamperes (±1 mA)

    GFCI devices are designed to trip when they sense a ground-fault current of approximately 4–6 mA (nominally 5 mA ±1 mA).

  7. Which conductor is NOT required to be protected by an overcurrent device under NEC 240.22?

    Answer: Grounded (neutral) conductors

    NEC 240.22 prohibits placing an OCPD in series with the grounded conductor unless the device opens all conductors simultaneously.