โ† All IPC Flashcard Decks

Sanitary Drainage Systems Flashcards

6 cards from real IPC practice questions. Tap to flip, then mark Knew It or Still Learning โ€” missed cards come back until you master them.

Read the first 6 Sanitary Drainage Systems flashcards as text
  1. According to the IPC, what is the minimum required slope for a 4-inch horizontal sanitary drainage pipe?

    Answer: 1/8 inch per foot

    IPC Table 704.1 specifies the minimum slope for horizontal drainage piping. For pipes with a diameter of 3 to 6 inches, the minimum slope required is 1/8 inch per foot (1-percent slope).

  2. A plumber is installing a new building sewer. According to the IPC, a cleanout is required at intervals of not more than:

    Answer: 100 feet

    IPC Section 708.3.2 states that building sewers shall be provided with cleanouts located not more than 100 feet apart. This allows for proper access for cleaning and maintenance of the sewer line.

  3. Which of the following fittings is generally prohibited for use in a sanitary drainage system to connect a horizontal drain to another horizontal drain?

    Answer: Sanitary tee

    According to IPC Section 706.3 and associated tables, a sanitary tee is restricted to connecting a horizontal drain to a vertical drain. Using it in a horizontal-to-horizontal application can impede flow and lead to stoppages.

  4. In a multistory building, a cleanout is required at the base of each waste or soil stack. The IPC requires the size of this cleanout for a 3-inch stack to be:

    Answer: The same nominal size as the pipe it serves

    IPC Section 708.7 specifies that cleanouts shall be the same nominal size as the pipe they serve up to 4 inches. Therefore, a 3-inch stack requires a 3-inch cleanout.

  5. A horizontal wet vent is being installed to serve two bathroom groups on the same floor. According to the IPC, which of the following statements is correct?

    Answer: Each wet-vented fixture drain must connect independently to the horizontal wet vent.

    IPC Section 912.1 requires that each fixture drain connecting to a horizontal wet vent does so independently. This ensures that the discharge from one fixture does not interfere with the venting of another.

  6. A plumber needs to install a horizontal drainage branch that will carry a total of 30 Drainage Fixture Units (DFUs). The pipe will be installed with a slope of 1/4 inch per foot. Based on IPC Table 710.1(2), what is the minimum required size for this horizontal branch?

    Answer: 3 inches

    According to IPC Table 710.1(2), a 3-inch horizontal branch pipe with a 1/4-inch-per-foot slope can handle a maximum of 42 DFUs. Since 30 DFUs is less than 42, a 3-inch pipe is the minimum required size. A 2 1/2-inch pipe at the same slope can only handle 21 DFUs, which is insufficient.