Wiring Methods and Materials Flashcards
7 cards from real IEC practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 Wiring Methods and Materials flashcards as text
What is the minimum bending radius for a 1-inch rigid metal conduit (RMC)?
Answer: 6 inches
NEC Table 344.24 requires a minimum bending radius of 6 times the trade size for 1-inch RMC, which equals 6 inches.
Which wiring method is specifically prohibited in commercial kitchens above a suspended ceiling where the space is used as a return air plenum?
Answer: Type AC cable (BX)
Type AC cable (BX) is not listed for use in plenum spaces; only wiring methods with plenum-rated cables or raceways are permitted per NEC 300.22(C).
When installing conductors in a conduit, what is the maximum fill percentage allowed for three or more conductors?
Answer: 31%
NEC Chapter 9, Table 1 limits conduit fill to 40% for two conductors and 31% for three or more conductors.
Type UF cable is specifically designed and listed for which application?
Answer: Direct burial in the earth without conduit
Type UF (Underground Feeder) cable is listed for direct burial applications per NEC Article 340.
What does NEC Article 358 govern?
Answer: Electrical metallic tubing (EMT)
NEC Article 358 covers the installation requirements for Electrical Metallic Tubing (EMT).
When securing nonmetallic-sheathed cable (NM) to a box, within how many inches of the box must a cable clamp or fitting be installed?
Answer: 12 inches
NEC 334.30(B) requires NM cable to be secured within 12 inches of a box or fitting where a clamp or fitting is required.
What is the minimum cover requirement for Schedule 80 PVC conduit installed under a residential driveway?
Answer: 12 inches
NEC Table 300.5 requires only 12 inches of cover for rigid nonmetallic conduit (Schedule 80) under a residential driveway.