Transformers and Distribution Systems Flashcards
7 cards from real IEC practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Transformers and Distribution Systems flashcards as text
What is the turns ratio of a single-phase transformer with a 480V primary winding and a 120V secondary winding?
Answer: 4:1
Turns ratio equals primary voltage divided by secondary voltage: 480V ÷ 120V = 4:1.
A 25 kVA, single-phase, 480V/240V transformer is operating at full load. What is the approximate rated secondary current?
Answer: 104A
Secondary current = kVA × 1,000 ÷ secondary voltage = 25,000 ÷ 240 ≈ 104A.
Which three-phase transformer connection provides a neutral conductor on the secondary side?
Answer: Delta-Wye
A Delta-Wye transformer provides a neutral from the center point of the wye-connected secondary windings.
According to NEC 450.3(B), a 480V transformer with a rated primary current of 9A requires primary overcurrent protection not exceeding what value?
Answer: 15A
NEC allows 125% of 9A = 11.25A; since no standard device matches that value, the next standard size of 15A is permitted.
What is the primary purpose of a K-rated transformer?
Answer: To handle harmonic currents from non-linear loads
K-rated transformers are built to withstand the additional heat generated by harmonic currents produced by non-linear loads such as computers and variable frequency drives.
A 75 kVA, three-phase, 480V/208Y/120V transformer is operating at full load. What is the approximate full-load secondary line current?
Answer: 208A
Full-load secondary current = kVA × 1,000 ÷ (secondary line voltage × √3) = 75,000 ÷ (208 × 1.732) ≈ 208A.
What type of transformer is designed to make small voltage adjustments, typically within ±5–20% of the supply voltage?
Answer: Buck-boost transformer
Buck-boost transformers are designed to raise (boost) or lower (buck) supply voltages by a small percentage to compensate for voltage variations.