Basic Electrical Standards Flashcards
7 cards from real IEC practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 Basic Electrical Standards flashcards as text
What is the minimum burial depth for rigid metal conduit (RMC) installed under a residential driveway?
Answer: 12 inches
NEC Table 300.5 requires RMC to be buried at least 12 inches under residential driveways.
According to the NEC, what color must the grounding conductor be identified by?
Answer: Green or bare
NEC 250.119 requires equipment grounding conductors to be green, green with yellow stripe, or bare.
A 20-ampere, 125-volt receptacle outlet is required in which of the following bathroom locations per NEC?
Answer: Within 3 feet of the sink basin
NEC 210.52(D) requires at least one receptacle within 3 feet of each sink basin in bathrooms.
What is the maximum voltage drop recommended by the NEC for branch circuits serving general loads?
Answer: 3%
NEC 210.19(A) informational note recommends keeping branch circuit voltage drop to 3% or less.
Under the NEC, which conductor insulation type is rated for use in wet locations?
Answer: THW
THW insulation is rated for use in both dry and wet locations, unlike THHN which is dry-location only.
What is the standard ampacity of a #12 AWG copper conductor with THHN insulation in a conduit with three current-carrying conductors?
Answer: 20 amperes
NEC Table 310.12 lists #12 AWG THHN copper at 20 amperes for up to three conductors in a raceway.
Which NEC article governs the installation of services, including service-entrance conductors?
Answer: Article 230
NEC Article 230 covers services, including service conductors, service equipment, and clearances.