  1. A technician notices that a system's high-side pressure is normal but the low-side pressure is higher than expected with low superheat. What is the most likely diagnosis?

    Answer: Metering device stuck open or failed open

    A metering device stuck open floods the evaporator, raising suction pressure and lowering superheat significantly.

  2. A residential heat pump operates correctly in cooling but has poor performance in heating mode. What should be suspected?

    Answer: Defrost control malfunction

    A faulty defrost control prevents the heat pump from clearing ice from the outdoor coil, drastically reducing heating capacity.

  3. During a service call, a technician measures 240V at a condenser but the unit does not start. The capacitor tests good. What should be checked next?

    Answer: Contactor contacts

    Burned or pitted contactor contacts may not pass current even when the contactor coil pulls in, preventing the compressor and fan from starting.

  4. An HVAC technician is troubleshooting a variable-speed air handler that is not communicating with the thermostat. What is the first step?

    Answer: Verify 24V power at the air handler control board

    Without 24V control voltage, the air handler's control board cannot operate or communicate, making power verification the essential first step.

  5. A gas furnace's pressure switch opens during operation. The flue pipe is clear and the inducer runs. What else should be checked?

    Answer: Condensate drain trap and tubing to the pressure switch

    A blocked condensate drain trap or kinked tubing to the pressure switch can cause a false negative-pressure reading, tripping the switch during operation.

  6. Subcooling is measured at 22°F on an R-410A system with a TXV. What condition does this indicate?

    Answer: Overcharge or restricted metering device

    Subcooling above 15°F on a TXV system typically indicates an overcharge or a restriction in the metering device causing liquid to back up in the condenser.

  7. A technician suspects a cracked heat exchanger in a gas furnace. Which test is the most reliable field method?

    Answer: Combustion analysis of CO levels

    Elevated carbon monoxide in the supply air or living space, verified with a combustion analyzer, is the most reliable indicator of a cracked heat exchanger allowing flue gases to enter the airstream.