Refrigerant Recovery and Handling Flashcards

7 cards from real HVAC practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 7 Refrigerant Recovery and Handling flashcards as text
  1. What is 'refrigerant banking' in the context of EPA Section 608 compliance?

    Answer: Holding recovered refrigerant in approved cylinders for later use or sale

    Refrigerant banking refers to storing recovered refrigerant in approved cylinders—either for reuse in the same system or for sending to a reclaimer.

  2. A system using R-22 has been retrofitted with a drop-in replacement. When recovering refrigerant from this system, what special consideration applies?

    Answer: The replacement refrigerant must be recovered into a separate, clearly labeled cylinder

    Retrofit refrigerants must be recovered separately from R-22 to prevent contamination and ensure each can be properly reclaimed or reused.

  3. What is the function of a 'passive' or 'system-dependent' recovery device?

    Answer: It uses the system's own compressor to push refrigerant into the recovery cylinder

    A passive (system-dependent) recovery device uses the system's own compressor to assist moving refrigerant into the recovery cylinder, requiring no separate recovery machine motor.

  4. What is the EPA-required maximum allowable standing vacuum level before a technician can open a system for service on appliances with charges between 200 lbs and 2,000 lbs of HCFC refrigerant?

    Answer: 4 inches Hg vacuum

    For systems with HCFC charges between 200 lbs and 2,000 lbs, EPA requires recovery to 4 inches Hg vacuum before the system can be opened.

  5. Which of the following best describes a 'critical leak' as defined by updated EPA Section 608 regulations for industrial process refrigeration?

    Answer: A leak exceeding 30% of charge per year

    For industrial process refrigeration, the EPA defines a critical leak as one exceeding 30% of total refrigerant charge per year.

  6. When using a recovery machine, why is it important to recover liquid refrigerant before vapor whenever possible?

    Answer: Liquid recovery is significantly faster since more mass is moved per cycle

    Recovering liquid refrigerant is much faster because liquid is denser—you move far more refrigerant mass per unit of time compared to vapor recovery.

  7. A DOT 4BA recovery cylinder has a tare weight of 14 lbs stamped on the collar. The current total weight is 50 lbs. What is the net refrigerant weight in the cylinder?

    Answer: 36 lbs

    Net refrigerant weight equals total weight minus tare weight: 50 lbs − 14 lbs = 36 lbs of refrigerant.