HVAC Cheat Sheet 2026

The 30 highest-yield HVAC facts, distilled from real exam questions. Print it, save it as a PDF, or study it here — free, no sign-up.

100 questions
120 min time limit
70.00% to pass
  1. What is the maximum fill level (by weight) for a recovery cylinder? 80%
  2. What is the purpose of vacuuming a mini-split system before charging? Both B and C — remove air/moisture and verify leak-free
  3. What troubleshooting method uses the process of elimination by testing components from 'most likely to least likely'? The probable-cause method
  4. What does a 'chilled water coil' use instead of direct refrigerant expansion? Cold water (typically 44-46°F) circulated from a central chiller
  5. What is the purpose of a disconnect switch near an outdoor HVAC unit? To provide a local means of de-energizing the unit for safe service work
  6. Which recovery method is fastest for recovering large amounts of liquid refrigerant? Liquid recovery first, then vapor
  7. What does 'ASHRAE 90.1' establish that BAS designers must follow? Energy efficiency standards including HVAC controls requirements for commercial buildings
  8. What is the most common cause of a clogged condensate drain line? Algae and biological growth in the drain line
  9. What is the purpose of a Variable Air Volume (VAV) box in a BAS-controlled system? To modulate airflow to individual zones to maintain zone temperature setpoints
  10. What type of coil is used in an air handler for the heating mode in a heat pump system? The same evaporator coil, which acts as a condenser during heating mode
  11. What is the function of a 'hard-start kit' (potential relay and start capacitor) on an air handler? It is not used on air handlers — only on compressors
  12. What is the primary advantage of a two-stage or variable-speed gas furnace? Improved comfort and efficiency by operating at lower capacity most of the time
  13. What unit is used to measure the cooling capacity of HVAC equipment in the US? BTU/hr or tons
  14. What is the purpose of indoor coil subcooling measurement? To determine if the refrigerant charge is correct when using the TXV charging method
  15. What is a low ambient kit and when is it needed for air conditioning systems? Controls that allow a cooling system to operate properly at low outdoor temperatures
  16. What is the purpose of the condensate drain pan in an air handler? To collect water condensed from humid air on the evaporator coil
  17. In HVAC, what does the term 'throw' refer to when selecting supply air diffusers? The horizontal distance the supply air travels before its velocity drops to 50 FPM
  18. What causes a compressor to 'trip' on its internal overload protector? Overheating of the motor windings due to excessive current or poor cooling
  19. What is 'infiltration' in the context of building load calculations? Uncontrolled air leakage into and out of a building through gaps and cracks
  20. What causes higher-than-normal wet-bulb temperature at the air handler inlet? High outdoor humidity and high indoor latent load
  21. What unit is used to measure airflow volume in HVAC duct systems? CFM (cubic feet per minute)
  22. What does a high-pressure switch in a refrigeration system do? Shuts down the compressor if refrigerant pressure exceeds a safe limit
  23. What is the correct refrigerant superheat at the evaporator outlet for a TXV-equipped system? 8-12°F (at the outlet of the coil)
  24. What safety hazard does 'liquid slugging' pose to a compressor? Hydraulic damage from incompressible liquid entering compression chambers
  25. What diagnostic information does measuring 'outdoor ambient temperature' provide during refrigerant charging? It's required for both superheat and subcooling charging charts to determine target values
  26. Which federal agency regulates the sale and use of refrigerants under Section 608? EPA
  27. What is the boiling point of R-410A at atmospheric pressure? -51.4°F (-46.3°C)
  28. What is 'demand-controlled ventilation' (DCV) and what sensor drives it? Outdoor air ventilation modulated based on actual occupancy, driven by CO2 sensors
  29. What is a 'non-condensable' gas in a refrigerant system, and why is it harmful? A gas like nitrogen or air that raises head pressure and reduces efficiency
  30. What does the term 'balance point' mean in heat pump system design? The outdoor temperature at which the heat pump output equals the building's heat loss
Turn these facts into recall: