  1. What minimum number of total air changes per hour (ACH) is required for general operating rooms per FGI Guidelines?

    Answer: 20 ACH

    FGI Guidelines require a minimum of 20 total air changes per hour for operating rooms, with at least 4 of those changes being outside air, to dilute airborne contaminants.

  2. What air pressure relationship is required in an operating room relative to adjacent spaces?

    Answer: Positive pressure to prevent corridor air from entering

    Operating rooms require positive air pressure relative to adjacent spaces so that clean filtered air flows outward, preventing contaminated corridor air from entering the sterile environment.

  3. Which spaces in a healthcare facility require negative air pressure relationships?

    Answer: Airborne infection isolation rooms and soiled utility areas

    Airborne infection isolation (AII) rooms require negative pressure to contain infectious airborne particles within the room and prevent their spread to adjacent patient care areas.

  4. What does HEPA stand for in the context of healthcare HVAC filtration systems?

    Answer: High Efficiency Particulate Air

    HEPA (High Efficiency Particulate Air) filters remove at least 99.97% of particles 0.3 microns or larger, providing critical protection against airborne pathogens in sensitive healthcare spaces.

  5. Why is humidity control critical in healthcare facility HVAC design?

    Answer: To prevent microbial growth, static electricity, and equipment damage that affect patient safety

    Humidity control in healthcare facilities prevents microbial growth from excess moisture, eliminates static electricity risks, protects sensitive equipment, and maintains patient safety and comfort.

  6. What is an Air Handling Unit (AHU) in a healthcare facility mechanical system?

    Answer: The central component that conditions and distributes air controlling temperature, humidity, and filtration

    An Air Handling Unit (AHU) is the central mechanical component that conditions air by controlling temperature, humidity, and filtration before distributing it throughout designated zones of a healthcare facility.