โ† All FST Flashcard Decks

Inspection Procedures Flashcards

7 cards from real FST practice questions. Tap to flip, then mark Knew It or Still Learning โ€” missed cards come back until you master them.

Read the first 7 Inspection Procedures flashcards as text
  1. Which document must a fire safety technician maintain to record all inspections, tests, and maintenance performed on a fire protection system?

    Answer: Inspection, test, and maintenance records

    NFPA standards require written inspection, test, and maintenance records to be maintained and made available to the AHJ upon request.

  2. A wet pipe sprinkler system is being inspected and several sprinkler heads are found within 18 inches of a storage pile. What is the concern?

    Answer: Obstruction to sprinkler distribution pattern

    Storage within 18 inches of sprinkler deflectors obstructs the discharge pattern and can prevent water from reaching the fire.

  3. During a quarterly inspection of a standpipe system, a technician finds a hose cabinet with a damaged hose. What is the correct action?

    Answer: Replace the damaged hose before closing the cabinet

    Damaged hose in a standpipe cabinet must be replaced immediately to ensure the standpipe system remains operationally ready.

  4. Which NFPA standard specifically governs the installation and inspection of portable fire extinguishers?

    Answer: NFPA 10

    NFPA 10 is the Standard for Portable Fire Extinguishers, covering installation, inspection, maintenance, and testing requirements.

  5. What is the maximum travel distance to a portable fire extinguisher for Class A hazards in ordinary hazard occupancies?

    Answer: 75 feet

    NFPA 10 requires Class A extinguishers to be placed so the maximum travel distance does not exceed 75 feet in ordinary hazard occupancies.

  6. When inspecting a fire alarm system, the technician discovers that a notification appliance circuit (NAC) has an open fault. What does this mean?

    Answer: The audible/visual alarm devices on that circuit will not operate

    An open NAC fault means the circuit to notification appliances (horns, strobes) is broken, so those devices will not operate during an alarm.

  7. A fire safety technician notes that a sprinkler system riser room is being used for storage. What is the primary concern?

    Answer: Access and egress for maintenance and emergency operations may be blocked

    Blocking access to the riser room prevents emergency response and routine maintenance, which is a code violation and safety hazard.