Inspection Procedures Flashcards
7 cards from real FST practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 Inspection Procedures flashcards as text
Which test method involves introducing smoke or aerosol into a smoke detector to verify its operational response?
Answer: Functional test
A functional test uses smoke or listed aerosol to verify the detector will respond and trigger an alarm signal.
A dry pipe valve accelerator is found to be leaking. What does this condition indicate?
Answer: Possible system actuation or air pressure loss
An accelerator leak may indicate the system has tripped, air pressure is dropping, or the accelerator itself is defective โ all requiring immediate investigation.
When inspecting portable fire extinguishers, what condition requires the extinguisher to be removed from service?
Answer: Broken or missing tamper seal
A broken or missing tamper seal indicates possible unauthorized discharge or tampering and requires the extinguisher be removed from service for inspection.
Under NFPA 72, how often must automatic smoke detectors in non-healthcare occupancies be tested?
Answer: Annually
NFPA 72 requires automatic smoke detectors in most occupancies to be tested annually using an approved method.
A technician inspects a kitchen hood suppression system and finds the fusible links have been painted. What action is required?
Answer: Replace the fusible links immediately
Painted fusible links must be replaced because the coating can prevent proper melting at the rated temperature, delaying system activation.
During inspection, a fire pump is found to run but delivers no water pressure. The most likely cause is:
Answer: Pump running in reverse rotation
A pump running in reverse rotation due to incorrect wiring will spin but produce little or no pressure, a common cause of this symptom.
What is the purpose of the annual 'trip test' performed on a dry pipe sprinkler system?
Answer: To verify the dry pipe valve operates properly and system drains within required time
The annual trip test verifies the dry pipe valve trips properly and that the system delivers water to the inspector's test connection within 60 seconds.