Free S-13 ITM Frequencies and Schedules Questions and Answers — Questions and Answers
Question 1: According to FDNY regulations, how often must control valves on a standpipe system be visually inspected?
- Daily
- Weekly (Correct answer)
- Monthly
- Annually
Correct answer: Weekly
Control valves must be visually inspected on a weekly basis to ensure they are in the normal position, accessible, and not leaking. This frequent check is critical for ensuring the system's readiness.
Question 2: A full flow test of the fire pump must be conducted at what frequency?
- Monthly
- Quarterly
- Annually (Correct answer)
- Every 5 years
Correct answer: Annually
An annual full flow test is required for fire pumps to verify that the pump and its driver are capable of supplying the required rated flow and pressure. This test ensures the pump will perform as designed during a fire event.
Question 3: How often is a hydrostatic test required for a standpipe system?
- Every year
- Every 3 years
- Every 5 years (Correct answer)
- Every 10 years
Correct answer: Every 5 years
NFPA 25 and FDNY rules require a full hydrostatic test of the standpipe system every 5 years. This test subjects the piping to high pressure to ensure there are no leaks or weaknesses that could cause a failure under operational pressure.
Question 4: The main drain test for a standpipe system should be performed at what minimum frequency?
- Weekly
- Monthly
- Quarterly
- Annually (Correct answer)
Correct answer: Annually
The main drain test is conducted annually to check the condition of the water supply. It involves recording the static and residual pressures to detect any significant changes that might indicate a problem like a partially closed valve or obstruction in the supply line.
Question 5: In a building with a dry standpipe system, how often must the air pressure and water pressure gauges be checked?
- Daily
- Weekly (Correct answer)
- Monthly
- Quarterly
Correct answer: Weekly
For dry pipe systems, it is crucial to check the air and water pressure gauges weekly. This ensures that the system has adequate supervisory air pressure to prevent accidental tripping and sufficient water pressure available when needed.
Question 6: Hose connections and caps must be inspected for what frequency to ensure they are not damaged or missing?
- Weekly
- Monthly
- Quarterly
- Annually (Correct answer)
Correct answer: Annually
Hose connections are inspected annually as part of the overall system inspection. This check ensures the threads are not damaged, gaskets are in place, and caps are securely fitted to prevent debris from entering the system.
According to FDNY regulations, how often must control valves on a standpipe system be visually inspected?