Regulations and Codes Flashcards
7 cards from real F80 practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 Regulations and Codes flashcards as text
Under NFPA 72, initiating devices in a fire alarm system must be installed so that a single open circuit fault will NOT disable more than how many devices?
Answer: One zone
NFPA 72 requires that a single open circuit fault disable no more than one initiating device zone, limiting the impact of wiring failures.
Which NYC agency has primary authority over fire alarm system certificate of fitness requirements for building supervisors?
Answer: FDNY (Fire Department of New York)
The FDNY issues and governs Certificates of Fitness, including the F80, for supervision of fire alarm systems in NYC.
According to NFPA 72, what color must the housing of a smoke detector with a sounder base be to indicate it is part of a fire alarm system?
Answer: Red or white
NFPA 72 requires that housings of detectors with integral sounders be red or white to distinguish them as fire alarm components.
Under the International Fire Code (IFC), a fire alarm system that is out of service for more than how many hours requires a fire watch?
Answer: 8 hours
The IFC requires implementation of a fire watch when a fire alarm system is out of service for more than 8 hours in a 24-hour period.
Per NFPA 72, notification appliances (horns, strobes) in a sleeping area must produce a minimum sound level of how many dBA at the pillow?
Answer: 75 dBA
NFPA 72 requires notification appliances to produce a minimum of 75 dBA at the pillow level in sleeping areas to awaken occupants.
What is the minimum age requirement to obtain an F80 Certificate of Fitness from the FDNY?
Answer: 18 years old
Applicants for the FDNY F80 Certificate of Fitness must be at least 18 years of age.
Under NFPA 72, a fire alarm control unit (FACU) must display a distinctive visible indication when the system is in which condition?
Answer: Alarm, supervisory, and trouble conditions
NFPA 72 requires the FACU to provide distinct visible indications for alarm, supervisory, and trouble conditions so operators can immediately identify system status.