← All F60 Flashcard Decks

Mixed Deck — All F60 Topics Flashcards

100 cards from real F60 practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 20 Mixed Deck — All F60 Topics flashcards as text
  1. What is the correct sequence for shutting down torch equipment at the end of a work period?

    Answer: Close cylinder valves first, bleed gas from lines through the torch, then close torch valves

    Closing cylinder valves first and bleeding lines through the torch ensures no pressurized gas remains trapped in hoses and regulators, preventing hose burnback.

  2. Which of the following is typically required when renewing an F-60 Certificate of Fitness?

    Answer: Passing a written examination administered by FDNY

    Renewal of the F-60 COF requires passing a written examination at FDNY headquarters.

  3. What should the Fire Guard do if the site supervisor instructs them to begin torch operations before the Hot Work Permit arrives?

    Answer: Refuse to allow operations to start until the valid permit is in hand and posted on site

    The Fire Guard must refuse to authorize commencement of operations until a valid Hot Work Permit is physically present and posted at the work site.

  4. Which extinguishing agent is most effective for Class B fires involving asphalt and propane during roofing operations?

    Answer: Dry chemical (ABC or BC rated)

    Dry chemical extinguishers rated BC or ABC are effective against flammable liquid and gas fires like those involving propane and asphalt.

  5. Under FDNY rules, how far must combustible materials be moved from the hot work area before a permit is valid?

    Answer: At least 35 feet

    FDNY requires all combustible materials to be moved at least 35 feet from the hot work zone, or protected with fire-resistant blankets, before a permit is considered valid.

  6. During torch operations, a fire guard notices smoke rising from behind a wall. The correct first action is to:

    Answer: Stop work, investigate the smoldering, and alert the torch operator

    Smoke behind a wall indicates possible hidden smoldering; work must be halted, the area investigated, and the torch operator notified immediately.

  7. A fire guard finds that the required fire extinguisher at the hot work site has a broken seal and an expired inspection tag. The correct action is:

    Answer: Stop work and replace the extinguisher with a properly inspected unit before allowing operations to resume

    An extinguisher with a broken seal or expired tag is not certified serviceable and must be replaced before any hot work may proceed.

  8. Which of the following is a primary duty of the "Responsible Person" in charge of the hot work program on a construction site?

    Answer: Authorizing and issuing hot work permits after verifying all safety conditions are met.

    The Responsible Person is designated by the owner to oversee the entire hot work program. A key function is to inspect the worksite, ensure all required precautions are in place, and then issue the internal hot work program authorization before work can commence.

  9. In the context of torch operations, what does the term 'hot work' refer to?

    Answer: Any work involving open flames, sparks, or heat sufficient to ignite combustibles

    Hot work includes any operation producing open flames, sparks, or heat capable of igniting nearby combustible materials.

  10. At what point should the fire guard conduct the FIRST inspection of the work area before torch operations begin?

    Answer: Immediately before operations begin to identify and address all hazards

    A pre-operation inspection of the work area is required to identify combustibles, verify extinguisher availability, and confirm safe conditions before the torch is lit.

  11. During a daily pre-work inspection, an F60 Fire Guard examines the portable fire extinguisher tag. Which feature, according to FDNY rules, helps verify the tag is authentic and not fraudulent?

    Answer: A hologram that displays an array of colors.

    To combat fraudulent servicing, the FDNY issues special tags with security features. These include a specific shape, size, color, and a hologram on the front to prevent fraudulent reproduction.

  12. If an F60 certificate holder discovers that their certificate expired last month, what should they do before serving as a fire guard?

    Answer: Renew the certificate with FDNY before performing fire guard duties

    An expired certificate is not legally valid; the holder must renew through FDNY before serving as a fire guard to avoid violations and liability.

  13. After a Hot Work Permit expires, can the same permit be extended to cover additional days of work?

    Answer: No, a new permit must be issued for each new work period

    Expired permits cannot be extended; a new Hot Work Permit must be issued for each authorized work period.

  14. After torch operations, the fire guard notices the wall behind the work area feels warm to the touch. What should they do?

    Answer: Treat it as a potential hidden fire and investigate or call FDNY

    A warm wall after torch work indicates possible fire inside the structure; this must be investigated immediately and FDNY notified if a fire is suspected.

  15. After a fire guard successfully extinguishes a small fire and notifies 911 as required, the site supervisor is eager to continue the torch operation. Hot work may not resume until what action has been taken?

    Answer: The responding FDNY officer inspects the area and declares it safe to proceed.

    Once the FDNY is notified and responds to an incident, they have authority over the scene. No work can resume until the responding fire officer has deemed the area safe. While replacing the extinguisher and documenting the incident are also necessary steps, the FDNY's approval is the overriding requirement before restarting operations.

  16. During torch operations on a roof, the fire guard notices tar paper beneath the work area beginning to smolder. What is the FIRST action?

    Answer: Stop work immediately and extinguish the smoldering material

    Smoldering materials must be addressed immediately by stopping work and extinguishing the threat before it escalates.

  17. Which of the following best describes the fire guard's ongoing duty during active torch operations?

    Answer: Continuously monitoring the work area and surrounding spaces for signs of fire, smoke, or heat

    The fire guard's core ongoing duty is active, continuous monitoring of the work area and surrounding spaces to detect any sign of fire, smoke, or excessive heat.

  18. During torch operations, where must the fire guard be positioned?

    Answer: In direct visual contact with the torch operator and work area

    The fire guard must maintain direct visual contact with the torch operator and work area at all times during operations.

  19. Before torch operations begin, the fire guard must inspect the hot work area and ensure combustible materials are removed or protected within what minimum radius?

    Answer: 35 feet

    FDNY regulations require combustible materials to be removed or protected within a 35-foot radius of the hot work area.

  20. What is the fire guard's responsibility regarding the torch operator's behavior during operations?

    Answer: To monitor the operator and stop work if unsafe practices are observed

    The fire guard has authority to stop operations if the torch operator engages in unsafe practices that create an unacceptable fire risk.