  1. Why should disposable (one-time-use) refrigerant cylinders never be used for recovery?

    Answer: They are not designed to be refilled and may rupture

    Disposable cylinders lack the construction and valves for refilling, so reusing them for recovery risks rupture and is prohibited by DOT.

  2. When transporting refrigerant cylinders in a service vehicle, how should they be secured?

    Answer: Secured in an upright position

    Cylinders should be secured upright to prevent movement, valve damage, and leaks during transport.

  3. A technician wants to confirm the identity of refrigerant in an unlabeled recovery cylinder at a known temperature. What is the best field method?

    Answer: Compare the cylinder pressure to a pressure-temperature chart after it stabilizes

    A pure refrigerant at a stable known temperature will show a pressure matching its saturation value on a P-T chart.

  4. A recovery cylinder at 75°F reads a pressure noticeably higher than the P-T chart value for the refrigerant it contains. What is the most likely cause?

    Answer: Noncondensable gases are present

    Noncondensables such as air add their partial pressure, raising cylinder pressure above the refrigerant's saturation pressure.

  5. Which release of refrigerant is considered a 'de minimis' release and NOT a violation of the venting prohibition?

    Answer: Small releases that occur during good-faith recovery using proper techniques and equipment

    De minimis releases are the small unavoidable amounts released while making good-faith attempts to recover refrigerant properly.

  6. When using a system-dependent (passive) recovery method on a small appliance with an inoperative compressor, what helps release refrigerant trapped in the oil?

    Answer: Accessing both high and low sides and tapping or heating the compressor

    With an inoperative compressor, accessing both sides and tapping or warming the compressor helps release refrigerant dissolved in the oil.

  7. Which group of refrigerants is classified as mildly flammable (A2L) and requires extra handling precautions such as spark-free tools and ignition-source control?

    Answer: R-32 and R-454B

    R-32 and R-454B are A2L refrigerants with low toxicity and lower flammability, requiring ignition-source precautions.