Core Concepts and Principles Flashcards
7 cards from real EPA practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Core Concepts and Principles flashcards as text
What is the maximum amount a refillable refrigerant cylinder should be filled?
Answer: 80% of its liquid capacity
Leaving 20% vapor space allows for liquid expansion as temperature rises.
What colors identify a DOT-approved refrigerant recovery cylinder?
Answer: Gray body with yellow top
Recovery cylinders are gray with yellow shoulders or tops.
How often must refillable refrigerant recovery cylinders be hydrostatically tested?
Answer: Every 5 years
DOT requires refillable cylinders to be hydrostatically retested every five years, with the date stamped on the cylinder.
Before disposing of a disposable (non-refillable) refrigerant cylinder, the technician should:
Answer: Recover remaining refrigerant to 0 psig and render the cylinder useless
Empty disposable cylinders are recovered to 0 psig, then punctured or marked empty before recycling as scrap metal.
What information must accompany a cylinder of used refrigerant being shipped to a reclaimer?
Answer: DOT classification tag and label showing refrigerant type and quantity
Shipped cylinders need DOT labeling and a tag identifying the refrigerant type and amount.
Why should refrigerant cylinders never be heated with an open flame or stored above 125°F?
Answer: Pressure can rise enough to rupture the cylinder
Heat raises cylinder pressure rapidly and can cause a rupture or explosion.
What gas should be used with a pressure regulator to pressurize a system for leak testing?
Answer: Dry nitrogen
Dry nitrogen is inert and safe, while oxygen or air can explode when mixed with compressor oil under pressure.