A pressure-temperature (P-T) chart for R-22 is primarily used to:
Answer: Determine saturation temperature at a given pressure
A P-T chart relates system pressure to the refrigerant's saturation temperature.
An R-22 system reads a head pressure far above the saturation pressure for its condensing temperature. The most likely cause is:
Answer: Non-condensables or overcharge
Abnormally high head pressure points to non-condensables or an overcharge.
Which symptom most strongly suggests a low refrigerant charge in a high-pressure system?
Answer: Low suction pressure with high superheat
An undercharge causes low suction pressure and elevated superheat.
A leak detection method that uses an electronic device sensitive to halogenated refrigerants is called a:
Answer: Electronic leak detector
Electronic leak detectors sense halogenated refrigerant escaping from leaks.
When pressurizing a high-pressure system for leak testing, which gas is acceptable to use with refrigerant as a trace?
Answer: Nitrogen
Dry nitrogen is the safe pressurizing gas for leak testing.
Excessive subcooling at the condenser outlet of an R-22 system often indicates:
Answer: Overcharge or restricted liquid line
High subcooling commonly results from overcharge or a liquid-line restriction.
What does a sight glass showing bubbles in the liquid line typically indicate?
Answer: Low charge or restriction causing flash gas
Bubbles in the sight glass indicate flash gas from low charge or a restriction.