Type II High-Pressure Systems Flashcards

7 cards from real EPA 608 609 practice questions. Tap to flip, then mark Knew It or Still Learning โ€” missed cards come back until you master them.

Read the first 7 Type II High-Pressure Systems flashcards as text
  1. A pressure-temperature (P-T) chart for R-22 is primarily used to:

    Answer: Determine saturation temperature at a given pressure

    A P-T chart relates system pressure to the refrigerant's saturation temperature.

  2. An R-22 system reads a head pressure far above the saturation pressure for its condensing temperature. The most likely cause is:

    Answer: Non-condensables or overcharge

    Abnormally high head pressure points to non-condensables or an overcharge.

  3. Which symptom most strongly suggests a low refrigerant charge in a high-pressure system?

    Answer: Low suction pressure with high superheat

    An undercharge causes low suction pressure and elevated superheat.

  4. A leak detection method that uses an electronic device sensitive to halogenated refrigerants is called a:

    Answer: Electronic leak detector

    Electronic leak detectors sense halogenated refrigerant escaping from leaks.

  5. When pressurizing a high-pressure system for leak testing, which gas is acceptable to use with refrigerant as a trace?

    Answer: Nitrogen

    Dry nitrogen is the safe pressurizing gas for leak testing.

  6. Excessive subcooling at the condenser outlet of an R-22 system often indicates:

    Answer: Overcharge or restricted liquid line

    High subcooling commonly results from overcharge or a liquid-line restriction.

  7. What does a sight glass showing bubbles in the liquid line typically indicate?

    Answer: Low charge or restriction causing flash gas

    Bubbles in the sight glass indicate flash gas from low charge or a restriction.