  1. Which refrigerant is most commonly associated with Type II high-pressure appliances?

    Answer: R-22

    R-22 is the classic high-pressure refrigerant covered under Type II certification.

  2. A high-pressure appliance with 50 lbs of charge that is not being disposed of must be repaired within how many days of a leak being detected?

    Answer: 30 days

    Leaks on appliances with 50+ lbs of charge generally must be repaired within 30 days.

  3. Before opening a high-pressure system for service, the refrigerant should be recovered to what level for a system with an open compressor?

    Answer: 4 inches of vacuum

    Open-drive compressors before 1993 require recovery to 4 inches of mercury vacuum.

  4. What is the required recovery vacuum level for a high-pressure appliance with more than 200 lbs of charge manufactured after November 15, 1993?

    Answer: 15 inches Hg vacuum

    Appliances over 200 lbs made after 1993 must be evacuated to 15 inches of mercury vacuum.

  5. Which device measures the depth of vacuum achieved during evacuation of a high-pressure system?

    Answer: Micron gauge

    A micron gauge accurately measures deep vacuum levels during evacuation.

  6. Non-condensable gases such as air in a high-pressure system primarily cause what problem?

    Answer: Higher head pressure

    Air and other non-condensables raise head pressure and reduce efficiency.

  7. What color is the high-pressure (liquid line) side gauge on a typical manifold gauge set?

    Answer: Red

    The red gauge reads the high-pressure side of the system.