EPA 608 Type III Practice Test 1 Flashcards

6 cards from real EPA 608 609 practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 6 EPA 608 Type III Practice Test 1 flashcards as text
  1. Which refrigerant is most commonly found in older low-pressure centrifugal chillers that require Type III EPA 608 certification?

    Answer: R-11

    R-11 (trichlorofluoromethane) is the classic CFC refrigerant used in older low-pressure centrifugal chillers. It operates well below atmospheric pressure at typical chiller conditions, which is the defining characteristic of Type III equipment. R-22 and R-410A are high-pressure refrigerants, and R-134a is a medium-pressure refrigerant.

  2. Under EPA Section 608 regulations, to what level must a technician recover refrigerant from a Type III low-pressure appliance before opening the system for service?

    Answer: 25 mm Hg absolute pressure

    EPA regulations require recovery from low-pressure appliances (Type III) to 25 mm Hg absolute pressure. This is a specific absolute pressure measurement — not a gauge pressure — reflecting that the system is already operating well below atmospheric. Recovering to 0 psig would still leave significant refrigerant in the system.

  3. How do technicians most reliably detect leaks in a Type III low-pressure chiller system during operation?

    Answer: Monitoring for a rise in system pressure caused by air infiltration

    Because Type III systems operate under vacuum, any leak allows atmospheric air to enter rather than refrigerant to escape. This air infiltration raises the internal pressure above the normal operating vacuum. Technicians watch for unexpected pressure rise as a primary leak indicator. Nitrogen pressurization is used for some leak checks but is not the primary operational detection method.

  4. What is the annual leak repair trigger rate established by EPA regulations for comfort cooling low-pressure chillers containing more than 50 pounds of refrigerant?

    Answer: 10% of the refrigerant charge per year

    EPA regulations set the leak repair trigger rate for comfort cooling equipment (which includes Type III centrifugal chillers) at 10% of the total charge per year. Once leak rates exceed this threshold, the equipment owner must repair the leaks within 30 days. Commercial refrigeration and industrial process equipment have higher trigger rates.

  5. When non-condensable gases such as air accumulate in a Type III low-pressure chiller, what is the primary operational consequence?

    Answer: Condensing pressure rises and system efficiency decreases

    Non-condensable gases like air do not condense in the condenser and therefore occupy space, causing condensing pressure to rise above normal. This elevated condensing pressure increases the work the compressor must do, reduces system capacity, and degrades overall efficiency. The purge unit is designed specifically to remove these gases and restore normal condensing pressure.

  6. A Type III chiller's purge unit is activating far more frequently than normal. What is the most likely cause?

    Answer: Air is leaking into the system at an abnormal rate

    The purge unit removes non-condensable gases (primarily air) that infiltrate the system because it operates under vacuum. Abnormally frequent purge activation means more air than usual is entering the system, which is a strong indicator of a leak in the vacuum-side components such as shaft seals, flanges, or fittings. This is an important diagnostic signal unique to low-pressure equipment.