EPA 608 609 System Evacuation and Charging Procedures 2 — Questions and Answers
Question 1: How must a blended (zeotropic) refrigerant be added to a system during charging?
- As vapor only through the suction line
- As liquid only (Correct answer)
- Either vapor or liquid — no difference
- As a 50/50 vapor-liquid mix
Correct answer: As liquid only
Zeotropic blends like R-410A and R-404A must be charged as liquid to prevent fractionation, which would alter the blend's composition and performance.
Question 2: What does the blue (low-side) gauge on a manifold gauge set measure?
- High-side discharge pressure
- Low-side suction pressure (Correct answer)
- Refrigerant vapor temperature
- Compressor oil pressure
Correct answer: Low-side suction pressure
The blue gauge measures low-side (suction) pressure, which corresponds to the evaporator pressure and is used to assess evaporator conditions.
Question 3: When charging a single-component refrigerant into an operating system, in what state should it enter the suction line?
- Liquid only
- Vapor (gas) only (Correct answer)
- Solid (dry ice)
- Supercritical fluid
Correct answer: Vapor (gas) only
Single-component refrigerants like R-22 can be safely charged as vapor into the suction line of a running system without risk of slugging the compressor.
Question 4: What does measuring superheat help a technician determine when charging a system with a fixed-orifice metering device?
- System efficiency rating
- Proper refrigerant charge level (Correct answer)
- Compressor oil level
- Filter drier condition
Correct answer: Proper refrigerant charge level
In fixed-orifice systems, suction line superheat directly reflects the refrigerant charge level — too high indicates undercharge, too low indicates overcharge.
Question 5: When using the subcooling method to verify charge in a TXV system, where is the liquid line temperature measured?
- At the evaporator inlet
- At the compressor suction port
- At the liquid line near the condenser outlet (Correct answer)
- At the compressor discharge port
Correct answer: At the liquid line near the condenser outlet
Subcooling is measured at the liquid line leaving the condenser, comparing actual temperature against saturation temperature at the measured high-side pressure.
Question 6: What manifold gauge readings typically indicate an overcharged refrigeration system?
- Both suction and discharge pressures below normal
- Both suction and discharge pressures above normal (Correct answer)
- Low suction and low discharge pressures
- Normal suction pressure with high discharge only
Correct answer: Both suction and discharge pressures above normal
Overcharging floods the evaporator with excess liquid refrigerant, raising suction pressure, while the condenser must reject extra heat, raising discharge pressure.
How must a blended (zeotropic) refrigerant be added to a system during charging?