Wiring & Installation Techniques Flashcards
7 cards from real EETC practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 Wiring & Installation Techniques flashcards as text
When connecting a 3-phase motor, swapping any two of the three phase leads will:
Answer: Reverse the direction of motor rotation
Swapping any two phase conductors on a 3-phase motor reverses the rotating magnetic field, causing the motor shaft to spin in the opposite direction.
What is the correct procedure when installing a new circuit breaker in a live panel?
Answer: Wear insulated gloves and use insulated tools with the main breaker off if possible
Safe work practice requires insulated PPE and tools; turning off the main breaker eliminates shock risk from bus bars during breaker installation.
A GFCI receptacle's 'Load' terminals protect:
Answer: Receptacles wired downstream on the same circuit
Devices connected to the LOAD terminals of a GFCI receptacle receive GFCI protection, extending protection to downstream outlets.
When installing conduit in a concrete pour, which type should be used?
Answer: PVC Schedule 40 or 80
PVC Schedule 40 or 80 conduit is used in concrete encasement because it resists corrosion from the alkaline concrete environment.
The ampacity of a conductor must be derated when more than three current-carrying conductors are bundled together because:
Answer: Heat accumulates and cannot dissipate as effectively
Bundled conductors share heat that cannot dissipate as quickly, reducing each conductor's safe current-carrying capacity.
What type of wire connector is listed for use with both aluminum and copper conductors in the same splice?
Answer: Purple wire nut (AL/CU listed)
Wire connectors listed for AL/CU (aluminum/copper) use contain anti-oxidant compound and are rated for dissimilar metal connections to prevent galvanic corrosion.
When installing outdoor receptacles exposed to weather, the cover must be rated:
Answer: In-Use (extra duty) cover providing protection with or without a plug inserted
NEC 406.9(B)(1) requires 'in-use' (extra duty) weatherproof covers for outdoor receptacles exposed to weather, protecting them even with cords plugged in.