Special Occupancies Flashcards
7 cards from real E2 practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 Special Occupancies flashcards as text
Under NEC Article 511, in a commercial repair garage, the area within 18 inches above floor level is classified as:
Answer: Class I, Division 2
NEC 511.3 classifies the area up to 18 inches above floor level in commercial garages as Class I, Division 2 due to heavier-than-air gasoline vapors.
In an aircraft hangar per NEC Article 513, the area within 5 feet horizontally from aircraft power plants is classified as:
Answer: Class I, Division 2
NEC 513.3 classifies areas within 5 feet horizontally from aircraft power plants and fuel tanks up to 5 feet above the upper surface as Class I, Division 2.
At a motor fuel dispensing facility (gas station), the space within the dispenser enclosure and within 18 inches horizontally in all directions from the dispenser is classified as:
Answer: Class I, Division 1
NEC 514.3 classifies the interior of the dispenser enclosure and the 18-inch zone around it as Class I, Division 1.
In spray application areas covered by NEC Article 516, the zone immediately surrounding open containers of flammable liquids is classified as:
Answer: Class I, Division 2 within 3 feet
NEC 516.3 classifies the area within 3 feet in all directions from open containers of flammable or combustible liquids as Class I, Division 2.
Under NEC Article 511, electrical equipment in a pit or depression in a commercial garage floor is subject to which classification?
Answer: Class I, Division 1 throughout the entire pit
NEC 511.3 requires pits and depressions in commercial garages to be classified as Class I, Division 1 because heavier-than-air vapors accumulate there.
Which NEC article governs electrical installations in bulk storage plants where flammable liquids are stored in above-ground tanks?
Answer: Article 515
NEC Article 515 covers bulk storage plants, which include facilities where flammable liquids are stored, blended, or redistributed in above-ground tanks.
In a commercial garage with adequate ventilation per NEC 511.3(B), the area above 18 inches from the floor is classified as:
Answer: Unclassified
When a commercial garage has adequate ventilation, the area above 18 inches from the floor is considered unclassified per NEC 511.3(B).