Pathways and Spaces Flashcards
7 cards from real DCI practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 Pathways and Spaces flashcards as text
What is the maximum number of 90-degree bends allowed in a single conduit run between pull points per NEC Article 358?
Answer: 4
The NEC limits a single conduit run to a maximum of 360 degrees of bends (equivalent to four 90-degree bends) between pull points.
Which TIA standard provides guidelines for telecommunications pathways and spaces in commercial buildings?
Answer: TIA-569
TIA-569 is the standard that addresses telecommunications pathways and spaces for commercial buildings.
A sleeve is best described as:
Answer: An opening through a wall, floor, or ceiling for passing cables
A sleeve is a round opening through a wall, floor, or ceiling that allows cables or conduits to pass through and must be firestopped after installation.
When installing a cable tray in an area accessible to the public, what is the minimum mounting height from the floor?
Answer: 7 feet
Cable trays installed in areas accessible to the public must be mounted at a minimum height of 7 feet (2.1 m) to prevent contact and ensure safety.
What is the primary purpose of a pull box in a conduit system?
Answer: To provide access for pulling and splicing cables
A pull box provides an access point in a conduit run for pulling cables through the system, especially on long runs or runs with multiple bends.
Which pathway type is formed by the structural cells of a concrete floor slab?
Answer: Cellular floor raceway
Cellular floor raceways are formed by the hollow cells within precast or poured concrete floor slabs, which serve as built-in cable pathways.
What does the acronym MER stand for in data center pathways and spaces terminology?
Answer: Main Equipment Room
MER stands for Main Equipment Room, which is the central space in a data center that houses core network and computing equipment.