  1. A heat pump in heating mode has frost building up on the outdoor coil when outdoor temperature is above 40°F. What is the MOST likely cause?

    Answer: Low refrigerant charge reducing evaporating temperature

    A low refrigerant charge drops the evaporating temperature below the frost point even in mild weather, causing premature frost accumulation on the outdoor coil.

  2. A technician uses electronic leak detection and finds a leak at the evaporator coil. What is the NEXT step before brazing the repair?

    Answer: Recover the refrigerant from the system

    Before any brazing or open-flame work, refrigerant must be completely recovered to prevent combustion of refrigerant decomposition products and to comply with EPA regulations.

  3. What is the MOST effective way to remove non-condensables from a refrigeration system?

    Answer: Recover refrigerant, evacuate the system, and recharge with virgin refrigerant

    Non-condensables cannot be separated in the field; the only correct method is full recovery, deep evacuation to remove air and moisture, and recharge with new refrigerant.

  4. A compressor with a cracked discharge valve reed will MOST likely exhibit:

    Answer: Low compression ratio and elevated suction pressure

    A cracked discharge valve allows high-pressure gas to re-expand into the cylinder, reducing pumping efficiency and causing elevated suction pressure and low compression ratio.

  5. When troubleshooting a system that repeatedly trips on high-pressure cutout, the technician should inspect the:

    Answer: Condenser airflow, refrigerant charge, and non-condensables

    High head pressure is caused by poor condenser heat rejection from blocked airflow, refrigerant overcharge, or non-condensables — all three must be checked.

  6. A technician notices the suction pressure is pulsing rhythmically on the gauge. This is MOST often caused by:

    Answer: TXV hunting due to improper superheat setting or bulb position

    TXV hunting occurs when the valve over-corrects repeatedly, causing cyclic swings in suction pressure that appear as gauge pulsation.

  7. After repairing a refrigerant leak and recharging a system, the technician should verify proper charge by checking:

    Answer: Superheat or subcooling depending on the metering device type

    Superheat is used to verify charge on fixed orifice systems, while subcooling is used on TXV systems; both methods confirm accurate refrigerant quantity in the circuit.