CRST Cheat Sheet 2026
The 30 highest-yield CRST facts, distilled from real exam questions. Print it, save it as a PDF, or study it here — free, no sign-up.
100 questions
120 min time limit
70% to pass
- What does a high-pressure control (HPC) do in a refrigeration system? → Shuts down the compressor when discharge pressure exceeds the set point
- A walk-in freezer door gasket is worn and not sealing properly. Besides temperature loss, what additional problem can result? → Excessive frost buildup on evaporator due to warm, moist air infiltration
- When a filter-drier becomes partially plugged, what is the MOST noticeable symptom? → Temperature drop across the filter-drier and bubbles in the sight glass
- What minimum refrigerant velocity is generally required in vertical suction line risers to ensure adequate oil return to the compressor? → 700-1,000 fpm
- How does root cause analysis improve repair effectiveness? → Identify underlying problems
- A technician discovers a system leaking R-22 at a rate of 25% per year. What is the required response timeline under EPA regulations? → Repair within 60 days of discovery
- When mounting a remote condenser on a rooftop, which installation requirement is most critical for proper oil return? → Pitch refrigerant lines toward the compressor and install traps on long vertical risers
- In a refrigeration ladder diagram, what symbol represents a normally open (NO) contact? → Two parallel vertical lines with a gap between horizontal lines
- What maintenance task should be performed on evaporator coil drain pans to prevent biological growth and drain blockage? → Add biocide tablets or clean and treat the pan and drain with approved algaecide
- When a CRST professional encounters an unexpected result during a procedure, the FIRST action should be to: → Stop, assess the situation, and determine whether to proceed or seek guidance
- Which type of fire extinguisher is appropriate for an electrical fire involving a refrigeration control panel? → Class C (CO2 or dry chemical)
- What type of capacitor provides an extra boost of starting torque for a PSC or CSCR compressor motor? → Start capacitor
- Under ASHRAE Standard 15, which refrigerant safety classification indicates the lowest toxicity and flammability? → A1
- What label information is required on a recovered refrigerant cylinder before it can be sent to a reclaimer? → Refrigerant type, whether it contains oil, and whether it is mixed with other refrigerants
- What is the PRIMARY purpose of obtaining CRST certification in Certified Refrigeration Service Technician? → To demonstrate verified competency and adherence to professional standards
- What is the PRIMARY purpose of obtaining CRST certification in Certified Refrigeration Service Technician? → To demonstrate verified competency and adherence to professional standards
- In what direction should horizontal suction lines be sloped to promote oil return? → 1/4 inch per foot sloping toward the compressor
- Which refrigerant property determines the saturation temperature at a given pressure? → Pressure-temperature relationship unique to each refrigerant
- A technician measures a 15°F superheat at the evaporator outlet and 80°F subcooling at the condenser outlet. What condition does this indicate? → Refrigerant overcharge
- What safety precaution must be taken before performing brazing work on a refrigeration system that contains or previously contained refrigerant? → Ensure the system is fully recovered and purged with nitrogen before applying heat
- Which OSHA standard specifically governs process safety management (PSM) for facilities using large quantities of ammonia refrigerant? → OSHA 29 CFR 1910.119
- What does the OSHA permissible exposure limit (PEL) for ammonia (R-717) in the workplace? → 50 ppm TWA
- When recovering refrigerant from a system with a hermetic compressor burnout, the technician should: → Use a dedicated recovery cylinder and filter to avoid cross-contamination
- What is the minimum vacuum level (in microns) required before charging most commercial refrigeration systems to ensure proper moisture removal? → 500 microns
- What is the standard voltage for a single-phase residential refrigeration compressor in the US? → 115V or 230V
- After repairing a refrigerant leak and recharging a system, the technician should verify proper charge by checking: → Superheat or subcooling depending on the metering device type
- Which refrigerant has an Ozone Depletion Potential (ODP) of zero and is commonly used in new commercial refrigeration systems in the US? → R-404A
- Which condition makes it legal under EPA Section 608 to vent a small amount of refrigerant during service? → De minimis releases that occur during good-faith repair attempts
- What role does proper diagnosis play in repairs? → Correctly identify issues
- What refrigerant is classified as R-717 and widely used in large industrial refrigeration systems? → Ammonia (NH3)