Instrumentation & Equipment Maintenance Flashcards
7 cards from real CPT practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Instrumentation & Equipment Maintenance flashcards as text
What is the primary difference between a Type J and a Type K thermocouple?
Answer: They differ in the metal alloy pairs used and their temperature measurement ranges
Type J uses iron–constantan (range ~-40 to 750°C) while Type K uses chromel–alumel (range ~-200 to 1260°C), giving them different sensitivities and temperature ranges.
In a proportional-integral-derivative (PID) controller, which tuning parameter eliminates steady-state offset (offset error)?
Answer: Integral time (Ti or reset)
The integral (reset) action integrates the error over time and continues to adjust the output until the error reaches zero, eliminating steady-state offset.
A technician notices that a pump mechanical seal is leaking. What is the most appropriate immediate action?
Answer: Notify supervision and prepare for planned seal replacement
A leaking mechanical seal should be reported and scheduled for replacement; operating with a compromised seal risks seal failure, product release, and potential fire/environmental hazard.
What effect does an increase in process fluid viscosity have on the flow measurement accuracy of a vortex flowmeter?
Answer: At high viscosity, the meter may not shed vortices reliably, causing measurement errors
Vortex flowmeters require turbulent flow (high Reynolds number) to shed vortices; high viscosity reduces the Reynolds number, potentially stopping vortex shedding and causing measurement failure.
What is the purpose of performing a 'bump test' on a gas detector?
Answer: Test the instrument's response to a known concentration of target gas to verify alarm functionality
A bump test exposes the detector to a challenge gas at a known concentration to confirm the sensor responds and alarms activate, verifying functional readiness without full calibration.
Which type of pump is best suited for handling high-viscosity fluids such as heavy oils or slurries?
Answer: Positive displacement pump
Positive displacement pumps (such as gear, progressive cavity, or piston types) maintain consistent flow regardless of viscosity and are better suited for thick or shear-sensitive fluids than centrifugal pumps.
A digital indicating controller displays 'INPUT FAIL' or an open-input alarm. What has most likely occurred?
Answer: The input sensor or wiring connection has failed or opened
An 'INPUT FAIL' alarm indicates the controller is not receiving a valid signal from the field sensor, most commonly due to a broken wire, failed transmitter, or open thermocouple.