  1. When inspecting an above-ground pool with a plug-in pump, the inspector should verify the pump cord is:

    Answer: Connected to a GFCI-protected receptacle within cord-and-plug distance specifications

    Cord-and-plug connected pool pumps must be plugged into GFCI-protected receptacles per NEC 680.22.

  2. A pool heater's metal cabinet must be bonded. The bonding connection point should be:

    Answer: A listed bonding lug or terminal on the heater cabinet

    Bonding connections must be made at listed lugs or terminals specifically intended for bonding to ensure reliable electrical continuity.

  3. During a CPI inspection, the inspector tests a GFCI receptacle near the pool using a GFCI tester and finds it does not trip. The correct action is to:

    Answer: Report it as a deficiency requiring immediate repair

    A GFCI that fails to trip when tested is defective and must be reported as a deficiency requiring replacement.

  4. What condition would cause an equipotential bonding system to be considered inadequate during a CPI inspection?

    Answer: The bonding conductor is broken and does not form a continuous loop to all required components

    A broken or discontinuous bonding conductor fails to equalize voltage, defeating the entire purpose of the bonding grid.

  5. A pool deck has embedded metal reinforcing steel. Per NEC 680.26, this rebar must be:

    Answer: Connected to the equipotential bonding grid if it is within 5 feet of the pool water

    Metal deck reinforcing within 5 feet of the pool water must be bonded to the equipotential grid even when encased in concrete per NEC 680.26.

  6. For a storable pool (above-ground), what electrical protection is required for any associated electrical equipment?

    Answer: GFCI protection on all electrical equipment and receptacles used with the pool

    NEC 680.10 requires GFCI protection for all electrical equipment associated with storable pools regardless of pool depth.

  7. A pool light niche is found cracked during inspection, allowing water to enter the fixture. The primary electrical hazard this creates is:

    Answer: Energized water in the pool if the lamp or socket is damaged

    Water in a cracked light niche can contact energized parts, potentially introducing voltage directly into the pool water and creating an electrocution hazard.