  1. What is the correct passive Profibus bus termination network configuration?

    Answer: 390 Ω pull-up to +5V, 220 Ω across A-B, 390 Ω pull-down to GND

    The Profibus termination network uses a 390 Ω resistor to +5V, a 220 Ω resistor across the differential pair, and a 390 Ω resistor to GND, providing impedance matching and idle-state line bias simultaneously.

  2. What is the consequence of operating a Profibus segment with no active bus termination at one or both ends?

    Answer: Signal reflections cause intermittent data corruption

    Without termination, signal energy is reflected from unterminated cable ends, creating superimposed waveforms that cause bit errors and intermittent communication faults.

  3. What measurements does a Profibus bus analyzer perform to assess physical layer signal quality?

    Answer: Signal voltage levels, noise margin, timing jitter, and reflection waveforms

    A Profibus bus analyzer captures and analyzes signal voltage, noise margin, jitter, and reflection signatures to give a complete picture of physical layer health.

  4. What is the primary purpose of a potential equalization bonding conductor in a Profibus installation?

    Answer: To equalize ground potentials between cabinets and reduce common-mode interference currents

    The potential equalization conductor minimizes the ground potential difference between interconnected cabinets, reducing common-mode currents that would otherwise flow through the cable shield and cause interference.

  5. What physical characteristic of Profibus Type A cable primarily limits the maximum achievable baud rate to 12 Mbit/s?

    Answer: Capacitance per unit length and resulting signal propagation delay

    The distributed capacitance (≤30 pF/m) combined with cable length creates an RC time constant that limits signal rise times, capping the practical baud rate at 12 Mbit/s.

  6. What is the maximum number of devices (stations) allowed on a single Profibus DP segment before a repeater is required?

    Answer: 32

    Profibus DP allows a maximum of 32 stations per segment (including masters and repeaters), limited by the cumulative electrical load of RS-485 transceiver unit loads on the bus.

  7. What common-mode voltage range must Profibus RS-485 transceivers tolerate without data corruption?

    Answer: ±7 V

    The RS-485 specification requires transceivers to operate correctly with common-mode voltages between -7 V and +12 V, accommodating the ground potential differences typical in industrial systems.