  1. Under OSHA's Process Safety Management (PSM) standard, which threshold quantity of flammable liquids triggers PSM coverage?

    Answer: 10,000 lb

    OSHA 29 CFR 1910.119 sets 10,000 lb as the threshold quantity for flammable liquids with a flashpoint below 73°F.

  2. Which EPA program requires facilities to develop Risk Management Plans (RMPs) for accidental chemical releases?

    Answer: Clean Air Act Section 112(r)

    Clean Air Act Section 112(r) established the RMP rule requiring facilities handling regulated substances above threshold quantities to file plans with EPA.

  3. A plant engineer notices that a solvent storage tank has a secondary containment dike that holds only 80% of the tank's capacity. Which standard is most likely violated?

    Answer: EPA SPCC requiring 110% containment

    EPA's Spill Prevention, Control, and Countermeasure (SPCC) rule requires secondary containment to hold at least 110% of the largest tank's capacity.

  4. Which document defines the Hierarchy of Controls for hazard mitigation, listed from most to least effective?

    Answer: ANSI Z10 occupational health and safety management standard

    ANSI/ASSP Z10 codifies the hierarchy: elimination, substitution, engineering controls, administrative controls, and PPE.

  5. When a plant generates hazardous waste and ships it offsite, which document must accompany the shipment?

    Answer: Uniform Hazardous Waste Manifest

    RCRA requires a Uniform Hazardous Waste Manifest to track hazardous waste from cradle to disposal.

  6. A permit-required confined space entry is underway when the atmospheric monitor alarms for oxygen-deficient conditions. What is the correct immediate action?

    Answer: Abort the entry and evacuate the entrant immediately

    OSHA 29 CFR 1910.146 requires immediate evacuation when a prohibited condition such as oxygen deficiency is detected during entry.

  7. Under the Clean Water Act NPDES permit program, what must a facility do if a discharge exceeds a permit effluent limit?

    Answer: Report the exceedance to the permitting authority per permit conditions

    NPDES permits include self-monitoring and reporting requirements; exceedances must be reported to the state or EPA permitting authority within the timeframe specified in the permit.