Portable Fire Extinguishers Flashcards
7 cards from real CFPS practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 Portable Fire Extinguishers flashcards as text
According to NFPA 10, what is the maximum mounting height (top of extinguisher) for a portable fire extinguisher with a gross weight not exceeding 40 lbs?
Answer: 5 feet
NFPA 10 Section 6.1.3.1 specifies that extinguishers weighing 40 lbs or less shall be installed so the top of the extinguisher is no more than 5 feet above the floor.
Under NFPA 10, stored pressure dry chemical fire extinguishers must undergo a complete internal examination at what interval?
Answer: Every 6 years
NFPA 10 requires that stored pressure extinguishers containing dry chemical agents undergo a complete internal examination every 6 years.
According to NFPA 10 Table 8.3.1, what is the required hydrostatic test interval for a carbon dioxide (CO2) fire extinguisher?
Answer: 5 years
NFPA 10 Table 8.3.1 specifies a 5-year hydrostatic test interval for carbon dioxide extinguishers due to their high operating pressures.
What does the acronym PASS represent in the proper operation of a portable fire extinguisher?
Answer: Pull, Aim, Squeeze, Sweep
PASS stands for Pull the pin, Aim at the base of the fire, Squeeze the handle, and Sweep the nozzle from side to side.
According to NFPA 10, which condition requires that a portable fire extinguisher be condemned and permanently removed from service?
Answer: A corroded cylinder shell that cannot be repaired or reconditioned
NFPA 10 Section 7.5.3 states that extinguishers with a corroded shell that cannot be cleaned, repaired, or reconditioned must be condemned and removed from service.
According to NFPA 10, what is the maximum travel distance to a Class B portable fire extinguisher in an extra hazard occupancy?
Answer: 30 feet
NFPA 10 Table 6.3.1.1 specifies a maximum travel distance of 30 feet to Class B extinguishers in extra hazard occupancies.
According to NFPA 10, what action is immediately required when a portable fire extinguisher has been partially discharged?
Answer: Immediately recharge or replace it
NFPA 10 Section 7.2.3 requires that any extinguisher that has been used or partially discharged be immediately recharged or replaced.