← All CFPS Flashcard Decks

Detection and Alarm Systems Flashcards

7 cards from real CFPS practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 7 Detection and Alarm Systems flashcards as text
  1. Under NFPA 72, which wiring class allows a single open or ground fault to render an entire circuit inoperable?

    Answer: Class B

    Class B circuits are not supervised for opens or shorts at every point, so a single fault can disable the entire circuit.

  2. A projected beam smoke detector measures which property to detect smoke?

    Answer: Reduction in infrared light intensity across a path

    Projected beam detectors measure attenuation of a light beam transmitted across a protected area; smoke reduces the received signal.

  3. NFPA 72 defines the Temporal-3 evacuation signal as:

    Answer: Three short pulses, pause, repeated

    Temporal Pattern 3 is 0.5-s ON, 0.5-s OFF, 0.5-s ON, 0.5-s OFF, 0.5-s ON, then 1.5-s OFF, repeated continuously.

  4. Which initiating device would be MOST appropriate to detect a slow smoldering fire in a large warehouse?

    Answer: Air-sampling (aspirating) smoke detector

    Air-sampling detectors actively draw air through a pipe network and can detect very low smoke concentrations produced by early-stage smoldering fires.

  5. What is the purpose of a duct smoke detector installed in an HVAC return-air duct?

    Answer: To prevent smoke from being recirculated through the HVAC system

    Duct detectors shut down the air-handling unit and close dampers to prevent smoke from spreading through the duct system to other areas.

  6. According to NFPA 72, a supervisory signal from a sprinkler control valve indicates:

    Answer: An abnormal condition requiring attention but not immediate evacuation

    Supervisory signals indicate off-normal conditions (such as a closed valve) that need correction but do not by themselves require evacuation.

  7. A flame detector that responds to radiant energy in the 4.3-micron CO₂ absorption band is classified as:

    Answer: Infrared (IR) detector

    The 4.3-micron band is a characteristic infrared emission of hot CO₂ produced in hydrocarbon flames, making this an IR flame detector.